Hoe u een gedistribueerd glasvezeltemperatuurmeetsysteem opzet

It is very simple to use, just need to perform the following four steps:

1) Insert temperature sensing optical cable

The connector of the temperature sensing optical cable must be correctly inserted into the device. The type of temperature sensing fiber optic cable connector is FC/APC. When inserting the optical cable plug, please make sure to align the protrusion on the plug with the groove in the socket, and then tighten the thread, zoals weergegeven in de volgende afbeelding:

When removing the connector from the adapter, please cover it with a protective cap to prevent dust from entering and affecting system performance.

2) Power on the device

Before powering on, connect the keyboard, mouse, and VGA display.

Power requirements: Wisselstroom 220V, 50Hz

Sluit het netsnoer aan op een stopcontact

Na aansluiting op de voeding, het systeem start automatisch op en voert het programma uit.

3) Wachten tot de zelftest van het systeem is voltooid

Nadat het apparaat is ingeschakeld, de software wordt automatisch geladen en uitgevoerd. Nadat de software is uitgevoerd, het start automatisch de detectie. Tijdens het detectieproces, de statusbalk wordt weergegeven: Systeem zelftest… Nadat de zelftest is voltooid, het wordt weergegeven: Normale collectie

4) Bekijk de temperatuur en het spectrum van glasvezelkabels

Schakel over naar de temperatuurcurvegrafiek en bekijk de realtime temperatuur van de optische kabel.

Schakel over naar de spectrale curvegrafiek en bekijk het spectrale signaal van de optische kabel.

1 Softwarebediening
3.1 Software hoofdinterface
3.2 Verzameling starten

Klik op het menu “Systeem | Verzameling starten” of klik op de “Verzameling starten” knop in de werkbalk.

U kunt de “application parametersto automatically collect data after the software starts.

3.3 Stop Collection

Klik op het menu “Systeem | Stop Collection”, or click theStop Collection” knop in de werkbalk.

3.4 Status bar information

Column 1: Display the current working status of the system.

During system self-test, het wordt weergegeven: Systeem zelftest

Normal operation is to display: normal collection

Column 2: Display the current channel number and collection time being collected

Column 3: Debugging Information

3.5 Spectral curve

Select the channel number in the channel dropdown box and selectspectral curvein the curve type dropdown box:

There are three curves in the spectral curve:

Red curve: Stokes signal curve;

Blue curve: Anti Stokes signal curve;

Green curve: the ratio curve of anti Stokes/Stokes;

The vertical axis represents the signal strength and voltage value; The horizontal axis represents the measurement position point.

The signal at around 250 points in the front is the internal fiber optic signal of the equipment, and the signal at the back is the measurement fiber optic signal.

The length of the optical fiber is displayed in red text above the curve, measured in points.

Display Zoom: Hold down the left mouse button while moving the mouse, move from the top left to the bottom right, release the left mouse button, and place it within the selected area for display. Click the left mouse button to display the access restored to the initial value.

3.6 Temperature curve

Select the channel number in the channel dropdown box and selecttemperature curvein the curve type dropdown box:

The vertical axis represents the temperature value, and the horizontal axis represents the number of position points.

The blue curve represents the temperature curve.

The red curve represents the temperature rise rate curve, measured in ℃/minute.

Wanneer de muis over de temperatuurcurve beweegt, de temperatuurwaarde en de temperatuurstijgingssnelheid die overeenkomen met het meetpunt op de muispositie worden in de rechterbovenhoek weergegeven.

Display Zoom: Hold down the left mouse button while moving the mouse, move from the top left to the bottom right, release the left mouse button, and place it within the selected area for display. Click the left mouse button to display the access restored to the initial value.

3.7 Glasvezelparameters

Klik op het menu: Instellingen | Glasvezelparameters, en de “Glasvezelparameters” dialoogvenster verschijnt,

Configureer onafhankelijk de glasvezelparameters voor elk kanaal.

Vanwege de verschillende eigenschappen zoals gewrichtsverlies, verliescoëfficiënt, verlies van fusiepunten, en aantal fusiepunten voor elke glasvezelkabel, het is noodzakelijk om na de constructie de glasvezelparameters voor elk kanaal afzonderlijk te corrigeren.

In de linkerlijst worden kanaalnamen weergegeven. Voordat u een kanaal instelt, selecteer het overeenkomstige kanaalnummer.

Uitgangspositie: De optische kabel komt overeen met de positie van de optische kabel in de software. As there is a reference fiber in the equipment, the starting position of the optical cable should be greater than the length of the reference fiber in the equipment. It is set up at the factory and does not require any modification.

Fiber length: reserved.

Demodulation coefficient: Temperature value T=a * x * x+b * x+c

A: Quadratic coefficient

B: Coefficient of first-order term

C: Constant coefficient

Import coefficient: The coefficient can be manually entered or directly imported from a file. ClickImport Coefficient” en de “Import Fiber Coefficient” dialoogvenster verschijnt:

Select a row corresponding to the fiber optic name and click the OK button.

Regional attributes: Fiber optic can be divided into multiple regions, and the attributes of each region can be configured separately. Regional attributes include: starting point of the region, temperature deviation, and transmission attenuation coefficient;

Add Area: Click theAddbutton to pop up theAreaparameter dialog box,

Starting point position: the starting point position of the region;

Temperature deviation coefficient: The temperature deviation value in this area, the temperature measurement value plus the deviation coefficient;

Transmission attenuation coefficient: The optical fiber transmission attenuation coefficient in this area.

Delete Area: Select the row of the area to be deleted and click the delete button.

Modify Area: Double click the row of the area you want to modify with the mouse, en de “Area Parameters” dialoogvenster verschijnt.

If the optical fiber has multiple fusion points, the loss of each fusion point will cause the temperature curve to not be straight. Daarom, different parameters, temperature deviation, and transmission attenuation coefficient need to be set for the area between each fusion point, zoals weergegeven in de volgende afbeelding:

The temperature curve corresponding to the above figure can be set in three regions, as shown in the table below:

Transmission loss coefficient of temperature deviation at the starting point of the region
1 300 0 0.000008
2 1000 2 0.0000085
3 2000 2 0.0000095

Transmission loss coefficient: affects the slope of the temperature curve, and adjusting the transmission loss coefficient of the channel can correct the slope of the temperature curve.

Voorbeeld 1: Transmission loss coefficient=0.00000920

In Example 1, the set transmission loss coefficient is exactly the actual transmission loss coefficient of the optical fiber, and the blue temperature curve is relatively flat.

Voorbeeld 2: Transmission loss coefficient=0.0001220

In Example 2, the set transmission loss coefficient is greater than the actual transmission loss coefficient, and the blue temperature curve slopes upwards.

Voorbeeld 3: Transmission loss coefficient=0.00000620

In Example 3, the set transmission loss coefficient is smaller than the actual transmission loss coefficient, and the blue temperature curve slopes downwards.

3.8 Application parameters

Klik op het menu: Instellingen | Application Parameters, en de “Application Parameters” dialoogvenster verschijnt

Save directory: The directory where historical data packets are saved. Click the “Selecteer” button and aBrowse Folder” dialoogvenster verschijnt, select the directory.

Save interval: Store every fixed time in seconds. If set to 0, data will not be saved.

Each time it is saved as a separate file, one channel corresponds to one file. The files for each channel are saved separately in the corresponding channel’s subdirectory. The file name rule is: CH channel number date time. dat. Voorbeeld: CH_101501002_12311.2dat.

Hide window when minimized: If checked, hide the window when clicking the minimize button and display the icon in the lower right corner of the taskbar.

Hide window after program operation: If checked, hide the window after program operation and display the icon in the lower right corner of the taskbar.

Start collection after program operation: If checked, collection will automatically start after program operation.

Language: Select the language for the program interface. Momenteel, only Chinese and English are supported. After switching languages, you must click theOK” knop, exit the program, and then run the program again to take effect.

Temperature display range: Set the range of the vertical axis in the temperature curve graph, with a default value of -50~150 ℃.

Voltage display range: Set the range of the vertical axis in the spectral curve graph, with a default value of -1 naar 4.

Temperature display starting point: Since there is a portion of optical fiber inside the device, if only the temperature of the temperature measuring optical cable needs to be displayed, this value can be set to shield the temperature of the optical fiber inside the device. The default value is the internal fiber length of the device.

Display temperature rise rate curve: If checked, the temperature rise quantity curve will be displayed simultaneously in the temperature curve graph, with a red curve; If not checked, only the temperature curve and blue curve will be displayed.

3.9 Historical data

Klik op het menu: Tools | Historical Data, en de “Historical Data” dialoogvenster verschijnt

Channel number: Select the channel number corresponding to the historical data to be queried;

Time range: Select the start and end times for querying historical data;

Query button: After setting the channel number and time range, click theQuerybutton to query the historical data files that meet the conditions;

File List: The file names of the query results are all displayed in the left list. Clicking on the corresponding file name will automatically open the data file and draw the data curve in the right curve graph.

Set display parameter button: Set the display parameters of the curve graph. After clicking, A “Display Parameters” dialoogvenster verschijnt,

Set the display range of the y-axis temperature in the curve graph, with a default value of -50~150.

3.10 Data Services

Set parameters: Klik op het menu: Tools | Data Services | Instellingen, en de “Server Parameters” dialoogvenster verschijnt,

TCP port number: default value is 9910

Auto start when program starts: If checked, the data service will be automatically started after the program runs;

Simulator: If there is no fiber optic cable, you can choose a simulator. De dataservice-interface simuleert een bepaald aantal glasvezeltemperatuurgegevens, wat handig is voor het debuggen van programma's.

Dienst starten: Klik op het menu: Tools | Data Services | Begin, en de “Server Parameters” dialoogvenster verschijnt. Nadat u heeft bevestigd dat de parameters correct zijn, click theOK” knop.

Dienst stopzetten: Klik op het menu: Tools | Data Services | Stop.