Üreticisi Fiber Optik Sıcaklık Sensörü, Sıcaklık İzleme Sistemi, Profesyonel OEM/ODM Fabrika, Toptancı, Tedarikçi.özelleştirilmiş.

E-posta: web@fjinno.net |

TempMerature İzleme/Yağa batırılmış trafo sıcaklık kontrol cihazı/

Trafo sıcaklığı, yağ seviyesi, ve basınç izleme cihazı

sıcaklık ölçümü :Range -45.0 ℃~200.0 ℃
Kesinlik -45.0 ℃~ 100.0 ℃± 2 °C
100.0℃~200.0℃ ±2%
Çözünürlük 0.1 °C

basınç ölçümü :Range: Absolute pressure 71~181Kpa
Accuracy ± 2Kpa
Resolution of 1Kpa

Oil level measurement:Range 0~-35mm
Accuracy ± 2mm
Resolution 1mm

work environment :Environmental temperature -40 ℃~+70 ℃
Environmental humidity ≤ 95% Sağ (25 °C)
Atmospheric pressure 80-110 Kpa (default 101Kpa)
Protection level IP68

Çalışma güç kaynağı:Power supply voltage DC12V-DC24V
Power consumption ≤ 5W

  • Ürün Detayları

To ensure the safe and stable operation of oil immersed transformers, data such as oil temperature, yağ seviyesi, akım, and voltage are often monitored. A transformer status online monitoring system is needed, which can monitor various key parameters of the equipment operation status at any time, timely understand the equipment status and quickly alarm in case of abnormal faults, manage and control in a timely manner, and effectively improve the reliability of transformer operation.
Based on the requirements and relevant technical standards for online monitoring of intelligent distribution transformers and combined substations, we have independently developed a three in one monitoring device for oil temperature, yağ seviyesi, and pressure. This device has the advantages of high safety, düşük maliyetli, good real-time performance, uygun kurulum, ve kolay bakım. It can be used for oil immersed transformers and combined substations, providing a good solution for online monitoring of oil temperature, yağ seviyesi, and pressure of power equipment. The monitoring device can achieve precise monitoring of transformer oil temperature oil level pressure and upload it to the intelligent fusion terminal in the substation area through RS-485.

Kategori İsim Specification Model Tanım
Sensor oil temperature oil level oil IB-YKTCF-OL/OP pressure three in one monitoring device
Accessory communication cable M12-L-4B-5M-BWG aviation plug connection shielded cable, default length 5 metre
Accessory Power Adapter DR-15-24 Input AC100V~240V, 50Hz/60Hz Output DC24V/15W
Integrated-Oil-Temperature-Level-and-Pressure-Tri-Parameter-Monitoring-Device Installation method of oil temperature oil level oil pressure three in one monitoring device

The monitoring device is installed in the traditional oil level gauge mounting hole, near the side edge of the transformer, as shown in Figure 3-3.
Installation tool: 68-72 crescent wrench.

(1)Monitoring device;
(2)Communication cable;
(3) Fusion terminal+power adapter (placed in the distribution cabinet);
(4)trafo

(1)Pressure relief valve cover

 

(2)Force release cover

 

(3)upper

 

(4)Nameplate

 

(5)Aviation socket

 

(6)Oil level observation window

 

(7)Casing (8)M52x2

 

(9)Oil float

 

(10)Sıcaklık sensörü

Integrated-Oil-Temperature-Level-and-Pressure-Tri-Parameter-Monitoring-Device
Integrated-Oil-Temperature-Level-and-Pressure-Tri-Parameter-Monitoring-Device Wire number renk wiring instructions
Oil-485A red Connected to Fusion Terminal: 9
Oil-485B blue Connected to fusion terminals: 10
+24V Brown Connect power adapter:+
-24V black Connect power adapter:-
Not: 1. The default standard configuration for the cable is a 5-meter-long 4-core shielded cable with a stainless steel bendable corrugated tube. 2. Other requirements can be customized.

Standart:

1. Production standard: Enterprise standard Q/IB 0001-2024
2. Certification Standard: ISO9001:2015 Uluslararası Kalite Yönetim Sistemi Belgelendirmesi
ISO14001:2015 Çevre Yönetim Sistemi Belgelendirmesi
ISO45001:2018 İş Sağlığı ve Güvenliği Yönetim Sistemi Belgelendirmesi
3. Experimental standard: IEC61000-4:2005 international standard
GB/T17626-2008 “Elektromanyetik Uyumluluk Testi ve Ölçüm Teknikleri” standart
According to the standard: DL/T 1498.1-2016; Q/GDW 1535-2015; DL/T 1432.1-2015

 

Önceki:

Sonraki:

Sorgu

    Mesaj bırakın