Transformer Winding & Indicadores de temperatura do óleo (WTI & FEITO)
FJINNO manufactures industrial indicadores de temperatura do enrolamento (WTI), indicadores de temperatura do óleo (FEITO), e fluorescent fiber optic winding sensors for oil-immersed power and distribution transformers. Whether your specification calls for power-free BWR2 / BWY2 mechanical gauges with 4-stage cooling and trip switches, synchronous Pt100 / 4–20 mA / RS485 telemetry, or dual-redundant direct optical hot-spot sensing, we supply factory-calibrated instrumentation built to IEC 60076 padrões.
How Winding Temperature Indicators (WTI) and Oil Temperature Indicators (FEITO) Work in Transformers
Every liquid-immersed substation transformer relies on two complementary gauges mounted on the tank side or marshalling box: um FEITO measuring real top-oil temperature, e um WTI simulating the copper winding hot-spot via a current-transformer (TC) imagem térmica.
WTI: Indicador de temperatura do enrolamento (BWR2 / BWR-04)
Tenrolamento = Tóleo + ΔTTC
A mechanical detector de temperatura do enrolamento cannot place a metallic bulb directly on live high-voltage copper. Em vez de, it sums the top-oil pocket temperature with a calibrated temperature rise (ΔT) gerado por um elemento de aquecimento alimentado pela corrente secundária do TC da bucha do transformador.
- 1. Transformador de corrente de bucha (TC): Fornece corrente secundária proporcional à carga (normalmente 0–5 A ou 0–1 A).
- 2. Bolso para termômetro & 3. Elemento Aquecedor: A bobina de aquecimento combinada dentro do transmissor composto aumenta a temperatura do bulbo proporcionalmente às perdas de cobre I²R.
- 4. Lâmpada sensora & 5. Capilar Blindado: A pressão de expansão do líquido aciona o ponteiro local, mão vermelha com memória de pico, e até 4 microinterruptores ajustáveis.
FEITO: Indicador de temperatura do óleo (OMS2 / OMS-803)
Óleo superior direto · M27×2
Um indicador de temperatura do óleo mede diretamente o óleo isolante mais quente na tampa superior do tanque através de um bolso de termômetro de aço cheio de óleo. Ele monitora o desempenho do sistema de resfriamento em massa, eficiência do radiador, and mineral/ester oil oxidation limits without requiring auxiliary power.
- Direct Immersion Sensing Bulb: Ø14 mm stainless bulb seated in an oil-filled M27×2 pocket (150–260 mm insertion depth) for fast thermal conduction.
- Compensação de temperatura ambiente: Dual-bellows mechanical linkage cancels outdoor cabinet temperature swings from −40°C to +55°C.
- Local + Remote Output: Drives cooling fans, alarme, and trip contacts locally while optionally sending Pt100, 4–20 mA, or RS485 signals to SCADA.
Transformer WTI & OTI Alarm, Ventilador de resfriamento & Trip Setpoints by Cooling Class
Select your transformer cooling class and adjust the load percentage below to review typical 4-stage relay switching behavior (K1–K4) and see how a thermal-image WTI compares against a direct fluorescent fiber optic hot-spot probe during heavy overload surges.
At rated load, BWR2 thermal-image WTI tracks close to steady-state winding temperature and stages cooling fans reliably without requiring auxiliary control power.
BWR2 Winding Temperature Indicators, BWY2 Oil Temperature Gauges & Direct Optical Upgrades
Every model below is manufactured and wet-bath calibrated at FJINNO. Choose round IP55 BWR2 / OMS2 dials for new utility transformers, rectangular BWR-04J. / OMS-803A units for drop-in fleet replacement, or add sondas de fibra óptica fluorescentes for direct winding verification.
Indicador de temperatura do enrolamento do transformador BWR2-04
Gabinete redondo de alumínio IP55 com transmissor composto CT compatível, ponteiro vermelho de temperatura de pico, e 4 microinterruptores independentes.
Indicador de temperatura do óleo do transformador BWY2-804
Termômetro com mostrador direto de óleo superior e capilar blindado em aço inoxidável, Lâmpada de bolso do tanque M27×2, e opções de transmissor SCADA remoto sincronizado.
BWR-04/06 Oil-Immersed Winding Temperature Controller
Classic rectangular die-cast case with front-accessible 4-channel setpoint drums for straightforward replacement on legacy substation transformers.
OMS-802 / 803A Oil Surface Temperature Controller
Rugged rectangular oil thermometer featuring 2 ou 3 independent control contacts (K1/K2/K3) and optional remote Pt100 resistance signal.
Oil-Immersed Transformer Pt100 Temperature Sensor
Precision Class A/B 3-wire Pt100 resistance probe engineered for oil-filled transformer pockets feeding RTUs, CLPs, and BWX digital meters.
Fluorescent Fiber Optic Winding Hot-Spot Probe
All-dielectric perforated PTFE probe embedded directly in winding spacers to eliminate thermal-image lag and verify real copper hot-spots.
Standard BWR2 / BWY2 Installation Dimensions
Engineered for direct mounting on standard IEC and utility oil-immersed transformer tank brackets with zero custom metalwork required:
- Dial Housing: Ø164 mm IP55 aluminum bezel, 3ר7 mm mounting pattern (144 milímetros × 210 mm centers).
- Tank Pocket Thread: Standard M27×2 (custom G3/4″ or NPT adapters available), 150–260 mm bulb immersion.
- Comprimento Capilar: 3 eu, 5 eu, 6 eu, 8 eu, 10 eu, or custom up to 15 m stainless steel braided armor.
- Remote Display Option: Pair with BWX digital panel meter (AC220V or AC/DC 100–264V, 4–20 mA / RS485).
Mechanical WTI/OTI vs. Digital Thermometers vs. Fluorescent Fiber Optic Winding Sensors
Traditional dial gauges and direct optical winding sensors are not mutually exclusive. Use this engineering comparison to decide when to specify a standalone BWR2 / BWY2 thermometer, um digital oil thermometer, ou um dual-redundant WTI + arquitetura de fibra óptica fluorescente.
| Selection Parameter | Mechanical WTI & FEITO (BWR2 / OMS2 / BWR-04) | Digital Oil / Winding Monitor (BWY-D804 / BWX + Pt100) | Fluorescent Fiber Optic Winding Sensor (Ponto de acesso direto) |
|---|---|---|---|
| Método de medição | Direct liquid-expansion top-oil bulb (FEITO) + CT heater simulation (WTI) | Electronic Pt100 RTD in oil pocket + digital CT current thermal model | Direct optical phosphor decay-time measurement on live HV winding copper |
| Auxiliary Power Needed? | Não — local dial & mechanical trip contacts operate without power | Sim (AC/DC 85–265 V or DC 24 V) | Sim (monitored by 1–64 ch optical host; commonly paired with BWR2 backup) |
| Transient Overload Response | 15–30 min thermal lag (estimates average winding rise, misses local blocked ducts) | Fast electronic display, but still bound by oil-pocket thermal-image model | < 1 segundo true direct hot-spot response inside actual winding spacers |
| SCADA & Saída de relé | 2–4 mechanical micro-switches + optional synchronous Pt100 / 4–20 mA / RS485 | Modbus RTU RS485, 4–20 mA, programmable alarm/trip relays, local LED/LCD | Modbus RTU RS485, 4–20 mA, programmable relays, optional IEC 61850 |
| Best-Fit Transformer Class | All distribution & substation oil-immersed transformers (mandatory local gauge) | Substations requiring centralized RTU telemetry and compact digital panels | Crítico 35 kV–500 kV power, aumento do gerador, retificador, forno & data-center transformers |
Field Installation Cases: Transformadores de Subestação, Winding Coils & Equipamento de alta tensão
Real on-site installations of FJINNO oil-immersed transformer sensors, winding fiber optic probes, and thermal protection systems across utility substations and industrial power equipment.
Substation Oil-Immersed Transformer Top-Cover Assembly
Integrated top-oil temperature, nível de líquido, and tank pressure sensing mounted directly on a live utility transformer cover.
Direct Transformer Winding Optical Probe Routing
Factory-embedded dielectric fluorescent probes with quick-connect ST leads providing EMI-free winding hot-spot protection.
High-Voltage Stator & Winding Thermal Instrumentation
Multi-point dielectric optical sensors installed directly in high-current winding slots immune to intense magnetic flux.
Substation Power Reactor Winding Monitoring
High-voltage air-core reactor coil monitoring protecting substation compensation banks against harmonic overheating.
All BWR2/BWR-04 indicadores de temperatura do enrolamento, BWY2/BWY-803 oil temperature indicators, and fluorescent fiber optic monitors are manufactured and wet-bath calibrated by Ciência Eletrônica de Inovação de Fuzhou&Companhia de tecnologia., Ltda. (FJINNO). Each unit ships with factory switch-point verification, IP55 enclosure inspection, and optional third-party type-test documentation.
- CEI 60076-2:2011 — Temperature rise limits and winding hot-spot measurement for liquid-immersed transformers.
- CEI 60076-7:2018 — Loading guide, top-oil limits, and hot-spot insulation aging curves for oil-immersed transformers.
Transformer WTI & OTI Winding & Oil Temperature Indicator FAQs
Direct answers for utility procurement engineers, fabricantes de transformadores, and substation maintenance teams.
1. What is the difference between a WTI and an OTI in a power transformer?
Uma OTI (OMS2-804 / OMS-803A) measures actual top-oil temperature in a tank pocket. A WTI (BWR2-04 / BWR-04J.) adds a CT-driven heating element to simulate the copper-to-oil temperature gradient so the dial reflects estimated winding temperature for cooling and trip protection.
2. What alarm and trip settings are normally used for OTI and WTI?
For typical mineral-oil ONAN/ONAF units under IEC 60076-7, OTI fan start is set around 55–65°C, alarm at 85–90°C, and trip at 95–100°C. WTI fan stages are normally 65°C / 80°C, alarm at 95–105°C, and trip at 110–115°C, adjusted to the transformer thermal class.
3. Can mechanical BWR2 and BWY2 gauges send data to our substation SCADA?
Sim. Alongside the power-free local dial and micro-switches, FJINNO BWR2 and BWY2 gauges support synchronous Pt100 resistance outputs, isolated 4–20 mA analog loops, or RS485 Modbus RTU modules for direct RTU/SCADA integration.
4. What pocket thread and capillary length should I specify?
Standard BWR2 and BWY2 probes use an M27×2 thread and 150–260 mm insertion depth (G3/4″ or NPT adapters available). Armored stainless steel capillaries are supplied in 3 eu, 5 eu, 6 eu, 8 eu, 10 eu, or custom lengths up to 15 eu.
5. When should we add fluorescent fiber optic probes alongside WTI/OTI dials?
Add direct fluorescent fiber optic probes on critical 35 kV–500 kV substation, aumento do gerador, forno, or data-center transformers where rapid load swings, ester oil, or dynamic rating require <1 s real copper hot-spot readings without thermal-image lag.
6. Do you supply drop-in replacements for legacy BWR-04 or BWY-802/803 units?
Sim. We manufacture both the classic rectangular BWR-04J. / OMS-802 / BWY-803 housings and the upgraded IP55 round BWR2 / BWY2 series, pre-configured with your required CT current ratio (1 UM / 5 UM), switch count, and capillary length.
Request BWR2 / BWY2 Drawings, Wiring Diagrams & Factory Quote
Send your transformer rating, aula de resfriamento (ONAN/ONAF/OFAF), comprimento capilar, Corrente secundária do TC (1 Um ou 5 UM), and whether you need remote 4–20 mA / RS485 or direct fluorescent fiber optic channels. Our engineering team responds with CAD drawings and pricing within 24 horas.
Sensores de temperatura de fibra óptica INNO ,sistemas de monitoramento de temperatura.