Producent Światłowodowy czujnik temperatury, System monitorowania temperatury, Profesjonalny OEM/ODM Fabryka, Hurtownik, Dostawca. dostosowany.

E-mail: web@fjinno.net |

Blogi

System monitorowania temperatury rozdzielnic oparty na fluorescencyjnym światłowodowym pomiarze temperatury

The switchgear temperature monitoring system based on fluorescent fiber optic temperature measurement is an intelligent system for real-time monitoring of critical parts of high-voltage switchgear (such as contacts, złącza szyn zbiorczych, końcówki kablowe, itp.). Its core adopts fluorescent fiber optic sensing technology, which can effectively handle complex environments such as strong electromagnetic interference, Wysokie napięcie, and compact space inside switchgear, providing reliable protection for safe equipment operation.

1. System Core Principle: Fluorescent Fiber Optic Temperature Measurement Technology

The core of fluorescent fiber optic temperature measurement is to use the temperature dependence of fluorescent substances to achieve temperature measurement. The principle is as follows:

  1. Excitation and Fluorescence Generation: The light source in the system (usually LED or laser) emits excitation light of specific wavelength (such as blue light), which is transmitted through optical fiber to the fluorescent probe (coated with fluorescent materials, such as rare earth doped materials) attached to the measured point;
  2. Fluorescence Decay Characteristics: After excitation, the fluorescent probe emits fluorescence (such as red light), and the decay time (fluorescence lifetime) or intensity of fluorescence changes with temperature (im wyższa temperatura, the faster the decay, the shorter the lifetime);
  3. Signal Detection and Temperature Calculation: The fluorescence signal is transmitted back to the signal processing unit through optical fiber, and the detector (such as photodiode, avalanche photodiode) detects the fluorescence decay curve, and converts the decay time into temperature value through algorithms (fluorescence lifetime has a monotonic function relationship with temperature, accuracy can reach ±0.5℃).

Wśród nich, the fluorescence lifetime temperature measurement method is mainstream (more interference-resistant compared to intensity method), as it is not affected by light source intensity fluctuations, optical fiber loss, connector attenuation and other factors, with higher stability.

2. System Component Structure

The fluorescent fiber optic switchgear temperature monitoring system usually consists of 4 parts, which work together to achieve temperature collection, przetwarzanie, transmission and monitoring:

Część Core Function
Fluorescent Fiber Optic Temperature Probe Directly contacts the measured point (such as switchgear contacts), receives excitation light and produces temperature-dependent fluorescence; uses high-temperature resistant, insulating material packaging, nadaje się do środowisk o wysokim napięciu.
Signal Processing Unit Includes light source drive, fluorescence signal reception (detector), signal amplification and filtering, fluorescence lifetime analysis modules, converting optical signals into temperature data.
Data Transmission Unit Transmits temperature data to upper computer through wired (such as RS485, Ethernetu) or wireless (such as LoRa, NB-IoT) metody; supports multi-point data multiplexing (time division/wavelength division multiplexing).
Upper Computer Monitoring System Realizes real-time temperature display, historical data storage, over-temperature alarms (sound/light/SMS/APP push), trend analysis and fault prediction, supports integration with power monitoring systems (SCADA).

3. System Core Advantages (Adapted to Switchgear Environment)

There are problems such as high voltage (10kV i więcej), silne zakłócenia elektromagnetyczne (surges and high-frequency electromagnetic fields generated by circuit breaker switching), compact space (dense internal components), dust/humidity changes inside switchgear. The advantages of fluorescent fiber optic systems are particularly prominent in this environment:

  1. Anti-strong Electromagnetic Interference: Optical fiber transmits optical signals, does not conduct electricity or radiate electromagnetic waves, completely unaffected by strong electromagnetic environment inside switchgear (such as closing inrush current, łuk), solving theelectromagnetic interference false alarmproblem of traditional electrical sensors (termoelement, PT100).
  2. High Voltage Insulation Safety: Optical fiber is an insulator (breakdown field strength >10kV/mm), probe has no electrical connection with signal processing unit, avoiding high voltage electric shock risk, suitable for direct installation on high voltage contacts, busbars and other parts.
  3. High Precision and Stability: Temperature measurement range is usually -40℃~200℃ (covering normal operation and fault temperature of switchgear), accuracy ±0.5℃~±1℃, long-term drift <0.1℃/year; fluorescent materials have strong anti-aging properties, service life can reach more than 10 lata.
  4. Miniaturization and Easy Installation: Optical fiber diameter is only 0.2~1mm, probe can be designed as patch type, typ sondy, can be embedded in narrow spaces of switchgear (such as contact gaps, końcówki kablowe), without affecting original equipment structure.
  5. Resistant to Harsh Environment: Optical fiber is oil-resistant, odporny na korozję, odporny na wibracje, can work stably in dusty, humid (IP65 protection) środowiska, suitable for long-term closed operation characteristics of switchgear.

4. System Key Technologies and Design Points

1. Multi-point Monitoring Multiplexing Technology:

Switchgear needs to monitor multiple critical parts (such as 3~6 contacts, 2~3 busbar joints). To reduce costs, the system usually adopts time division multiplexing (TDM) or wavelength division multiplexing (WDM) technologia:

  • TDM: Through timing control, multiple probes share the same light source and detector in time division, suitable for 8~32 point monitoring;
  • WDM: Different probes correspond to different wavelengths of fluorescence, signals are distinguished through optical splitters, suitable for high-precision, multi-channel scenarios.

2. Anti-interference and Reliability Design:

  • Optical fiber path optimization: Avoid optical fiber bending radius too small (usually ≥20 times optical fiber diameter), reduce optical loss; install stainless steel protective sleeves at critical parts to improve mechanical strength.
  • Signal processing anti-noise: Use phase-locked amplification, filtering algorithms (such as Kalman filtering) to suppress environmental light and circuit noise, ensure accurate detection of weak fluorescence signals (μW level).
  • Calibration mechanism: Multi-point calibration through high and low temperature boxes before factory delivery, field support for regular online calibration (compared with standard thermocouples).

5. System Functions and Application Value

Podstawowe funkcje

  • Monitorowanie w czasie rzeczywistym: Dynamically display temperature of each measuring point (refresh frequency 1~10Hz), support local touch screen and remote monitoring center (such as SCADA system) linkage.
  • Early warning and alarm: Set three-level thresholds (normal/warning/over-limit), trigger sound and light alarms, SMS/APP push notifications to maintenance personnel.
  • Data traceability: Store historical data for more than 1 rok (temperatura, time, zapisy alarmowe), support curve analysis and fault tracing.
  • Trend prediction: Through machine learning algorithms (such as LSTM) to analyze temperature change trends, predict potential overheating risks 7~30 days in advance.

Application Value

  • Ensure equipment safety: Timely discover overheating caused by poor contact, starzenie się, itp. (such as contact temperature exceeding 80℃ may cause insulation aging), prevent short circuits, fires and other accidents.
  • Reduce operation and maintenance costs: Replace traditionalregular power outage inspection”, achieve condition-based maintenance, reduce power outage time (can reduce 2~3 unplanned power outages annually).
  • Adapt to smart grid: Meet the development needs of “podstacje cyfrowe”, provide key data support for switchgear health assessment.

6. Comparison with Other Temperature Measurement Technologies

Compared with traditional temperature measurement solutions for switchgear (such as infrared, czujniki bezprzewodowe, termopary), fluorescent fiber optic systems have significant advantages:

Technology Type Wady Advantages of Fluorescent Fiber Optic System
Infrared Temperature Measurement Depends on unobstructed line of sight, cannot monitor critical parts when switchgear internal structure is complex. Optical fiber can be flexibly arranged, directly contacts measured points, unaffected by obstruction.
Czujniki bezprzewodowe Communication easily interrupted in strong electromagnetic environment, short battery life (1~3 years replacement required). No electromagnetic interference, passive probe (no power supply required), maintenance-free.
Termoelement Metal leads easily affected by electromagnetic interference, high insulation risk in high voltage environment. Optical fiber insulation, no electromagnetic coupling, suitable for high voltage scenarios.

Streszczenie

The switchgear temperature monitoring system based on fluorescent fiber optic temperature measurement, with its characteristics of anti-strong electromagnetic interference, izolacja wysokiego napięcia, i wysoką precyzję, perfectly adapts to the complex operating environment of switchgear. It is one of the core technologies for realizing the closed-loop management ofcondition sensing-early warning-operation and maintenanceof power equipment, and is of great significance for improving power grid reliability.

zapytanie

Światłowodowy czujnik temperatury, Inteligentny system monitorowania, Producent rozproszonych światłowodów w Chinach

Fluorescencyjny pomiar temperatury za pomocą światłowodu Fluorescencyjne, światłowodowe urządzenie do pomiaru temperatury Rozproszony, fluorescencyjny, światłowodowy system pomiaru temperatury

Poprzednia: