כיצד להגדיר מערכת מדידת טמפרטורה מבוזרת בסיבים אופטיים

It is very simple to use, just need to perform the following four steps:

1) Insert temperature sensing optical cable

The connector of the temperature sensing optical cable must be correctly inserted into the device. The type of temperature sensing fiber optic cable connector is FC/APC. When inserting the optical cable plug, please make sure to align the protrusion on the plug with the groove in the socket, and then tighten the thread, as shown in the following figure:

When removing the connector from the adapter, please cover it with a protective cap to prevent dust from entering and affecting system performance.

2) Power on the device

Before powering on, connect the keyboard, mouse, and VGA display.

Power requirements: AC 220V, 50הרץ

Connect the power cord to a power outlet

After connecting to the power supply, the system automatically starts up and runs the program.

3) ממתין לסיום הבדיקה העצמית של המערכת

לאחר הפעלת המכשיר, התוכנה נטענת ופועלת באופן אוטומטי. לאחר הפעלת התוכנה, זה מתחיל בזיהוי אוטומטי. במהלך תהליך האיתור, שורת המצב מוצגת: בדיקה עצמית של המערכת… לאחר השלמת הבדיקה העצמית, זה מציג: אוסף רגיל

4) הצג את הטמפרטורה והספקטרום של כבל סיבים אופטיים

עבור לגרף עקומת הטמפרטורה והצג את הטמפרטורה בזמן אמת של הכבל האופטי.

עבור לגרף העקומה הספקטרלית והצג את האות הספקטרלי של הכבל האופטי.

1 תפעול תוכנה
3.1 ממשק ראשי תוכנה
3.2 מתחיל איסוף

לחץ על התפריט “מַעֲרֶכֶת | התחל איסוף” או לחץ על “התחל איסוף” כפתור בסרגל הכלים.

אתה יכול להגדיר את “פרמטרים של יישום” לאסוף נתונים אוטומטית לאחר הפעלת התוכנה.

3.3 עצור איסוף

לחץ על התפריט “מַעֲרֶכֶת | עצור איסוף”, או לחץ על “עצור איסוף” כפתור בסרגל הכלים.

3.4 מידע על שורת המצב

עַמוּדָה 1: Display the current working status of the system.

During system self-test, זה מציג: בדיקה עצמית של המערכת

Normal operation is to display: normal collection

עַמוּדָה 2: Display the current channel number and collection time being collected

עַמוּדָה 3: Debugging Information

3.5 Spectral curve

Select the channel number in the channel dropdown box and selectspectral curvein the curve type dropdown box:

There are three curves in the spectral curve:

Red curve: Stokes signal curve;

Blue curve: Anti Stokes signal curve;

Green curve: the ratio curve of anti Stokes/Stokes;

The vertical axis represents the signal strength and voltage value; The horizontal axis represents the measurement position point.

The signal at around 250 points in the front is the internal fiber optic signal of the equipment, and the signal at the back is the measurement fiber optic signal.

אורך הסיב האופטי מוצג בטקסט אדום מעל העקומה, נמדד בנקודות.

תצוגה זום: החזק את לחצן העכבר השמאלי לחוץ בזמן הזזת העכבר, לעבור מלמעלה משמאל לימין למטה, שחרר את לחצן העכבר השמאלי, והצב אותו בתוך האזור שנבחר לתצוגה. לחץ על לחצן העכבר השמאלי כדי להציג את הגישה ששוחזרה לערך ההתחלתי.

3.6 עקומת טמפרטורה

Select the channel number in the channel dropdown box and select “עקומת טמפרטורה” in the curve type dropdown box:

הציר האנכי מייצג את ערך הטמפרטורה, והציר האופקי מייצג את מספר נקודות המיקום.

העקומה הכחולה מייצגת את עקומת הטמפרטורה.

העקומה האדומה מייצגת את עקומת קצב עליית הטמפרטורה, נמדד ב℃/דקה.

כאשר העכבר נע על עקומת הטמפרטורה, the temperature value and temperature rise rate corresponding to the measurement point at the mouse position will be displayed in the upper right corner.

תצוגה זום: החזק את לחצן העכבר השמאלי לחוץ בזמן הזזת העכבר, לעבור מלמעלה משמאל לימין למטה, שחרר את לחצן העכבר השמאלי, והצב אותו בתוך האזור שנבחר לתצוגה. לחץ על לחצן העכבר השמאלי כדי להציג את הגישה ששוחזרה לערך ההתחלתי.

3.7 Fiber optic parameters

לחץ על התפריט: Settings | Fiber Optic Parameters, ואת “Fiber Optic Parametersdialog box will pop up,

Independently configure the fiber parameters for each channel.

Due to the different properties such as joint loss, loss coefficient, fusion point loss, and number of fusion points for each fiber optic cable, it is necessary to separately correct the fiber optic parameters for each channel after construction.

The left list displays channel names. Before setting a channel, select the corresponding channel number.

Starting position: The optical cable corresponds to the position of the optical cable in the software. As there is a reference fiber in the equipment, the starting position of the optical cable should be greater than the length of the reference fiber in the equipment. It is set up at the factory and does not require any modification.

אורך סיבים: reserved.

Demodulation coefficient: Temperature value T=a * x * x+b * x+c

א: Quadratic coefficient

ב: Coefficient of first-order term

c: Constant coefficient

Import coefficient: The coefficient can be manually entered or directly imported from a file. ClickImport Coefficient” ואת “Import Fiber Coefficientdialog box will pop up:

Select a row corresponding to the fiber optic name and click the OK button.

Regional attributes: Fiber optic can be divided into multiple regions, and the attributes of each region can be configured separately. Regional attributes include: starting point of the region, temperature deviation, and transmission attenuation coefficient;

Add Area: Click the “לְהוֹסִיף” button to pop up theAreaparameter dialog box,

Starting point position: the starting point position of the region;

Temperature deviation coefficient: The temperature deviation value in this area, the temperature measurement value plus the deviation coefficient;

Transmission attenuation coefficient: The optical fiber transmission attenuation coefficient in this area.

Delete Area: Select the row of the area to be deleted and click the delete button.

Modify Area: Double click the row of the area you want to modify with the mouse, ואת “Area Parametersdialog box will pop up.

If the optical fiber has multiple fusion points, the loss of each fusion point will cause the temperature curve to not be straight. לָכֵן, different parameters, temperature deviation, and transmission attenuation coefficient need to be set for the area between each fusion point, as shown in the following figure:

The temperature curve corresponding to the above figure can be set in three regions, as shown in the table below:

Transmission loss coefficient of temperature deviation at the starting point of the region
1 300 0 0.000008
2 1000 2 0.0000085
3 2000 2 0.0000095

Transmission loss coefficient: affects the slope of the temperature curve, and adjusting the transmission loss coefficient of the channel can correct the slope of the temperature curve.

דוּגמָה 1: Transmission loss coefficient=0.00000920

In Example 1, the set transmission loss coefficient is exactly the actual transmission loss coefficient of the optical fiber, and the blue temperature curve is relatively flat.

דוּגמָה 2: Transmission loss coefficient=0.0001220

In Example 2, the set transmission loss coefficient is greater than the actual transmission loss coefficient, and the blue temperature curve slopes upwards.

דוּגמָה 3: Transmission loss coefficient=0.00000620

In Example 3, the set transmission loss coefficient is smaller than the actual transmission loss coefficient, and the blue temperature curve slopes downwards.

3.8 Application parameters

לחץ על התפריט: Settings | Application Parameters, ואת “Application Parametersdialog box will pop up

Save directory: The directory where historical data packets are saved. Click theSelectbutton and aBrowse Folderdialog box will pop up, select the directory.

Save interval: Store every fixed time in seconds. If set to 0, data will not be saved.

Each time it is saved as a separate file, one channel corresponds to one file. The files for each channel are saved separately in the corresponding channel’s subdirectory. The file name rule is: CH channel number date time. dat. דוּגמָה: CH_101501002_12311.2dat.

Hide window when minimized: If checked, hide the window when clicking the minimize button and display the icon in the lower right corner of the taskbar.

Hide window after program operation: If checked, הסתר את החלון לאחר פעולת התוכנית והצג את הסמל בפינה הימנית התחתונה של שורת המשימות.

התחל איסוף לאחר פעולת התוכנית: If checked, האיסוף יתחיל אוטומטית לאחר פעולת התוכנית.

שָׂפָה: בחר את השפה עבור ממשק התוכנית. כַּיוֹם, רק סינית ואנגלית נתמכות. לאחר החלפת שפה, עליך ללחוץ על “OKbutton, לצאת מהתוכנית, ולאחר מכן הפעל את התוכנית שוב כדי להיכנס לתוקף.

טווח תצוגת טמפרטורה: הגדר את טווח הציר האנכי בגרף עקומת הטמפרטורה, עם ערך ברירת מחדל של -50~150 ℃.

טווח תצוגת מתח: הגדר את הטווח של הציר האנכי בגרף העקומה הספקטרלית, עם ערך ברירת מחדל של -1 אֶל 4.

נקודת התחלה של תצוגת טמפרטורה: מכיוון שיש חלק של סיב אופטי בתוך המכשיר, if only the temperature of the temperature measuring optical cable needs to be displayed, this value can be set to shield the temperature of the optical fiber inside the device. The default value is the internal fiber length of the device.

Display temperature rise rate curve: If checked, the temperature rise quantity curve will be displayed simultaneously in the temperature curve graph, with a red curve; If not checked, only the temperature curve and blue curve will be displayed.

3.9 Historical data

לחץ על התפריט: Tools | Historical Data, ואת “Historical Datadialog box will pop up

Channel number: Select the channel number corresponding to the historical data to be queried;

Time range: Select the start and end times for querying historical data;

Query button: After setting the channel number and time range, click theQuerybutton to query the historical data files that meet the conditions;

File List: The file names of the query results are all displayed in the left list. Clicking on the corresponding file name will automatically open the data file and draw the data curve in the right curve graph.

Set display parameter button: Set the display parameters of the curve graph. After clicking, א “Display Parametersdialog box will pop up,

Set the display range of the y-axis temperature in the curve graph, with a default value of -50~150.

3.10 Data Services

Set parameters: לחץ על התפריט: Tools | Data Services | Settings, ואת “Server Parametersdialog box will pop up,

TCP port number: default value is 9910

Auto start when program starts: If checked, the data service will be automatically started after the program runs;

Simulator: If there is no fiber optic cable, you can choose a simulator. The data service interface simulates a certain number of fiber optic temperature data, which is convenient for program debugging.

Start Service: לחץ על התפריט: Tools | Data Services | Start, ואת “Server Parametersdialog box will pop up. לאחר אישור שהפרמטרים נכונים, click theOKbutton.

הפסקת שירות: לחץ על התפריט: Tools | Data Services | לְהַפְסִיק.