Dissolved Gas Analysis — Oil Chromatography Monitoring, Fault Diagnosis & Online DGA Systems

  • Dissolved gas analysis (DGA) is the most widely accepted diagnostic technique for detecting incipient internal faults in oil-filled power transformers.
  • Different fault types — thermal overheating, partial discharge, and arcing — produce characteristic gases that can be identified through oil gas chromatography.
  • Established diagnostic methods including the Key Gas Method, IEC 60599 three-ratio method, and Duval Triangle enable systematic fault classification from DGA data.
  • Online DGA monitoring systems using oil chromatograph technology provide continuous, real-time dissolved gas tracking with RS485/Modbus integration to SCADA.
  • This article covers fault gas generation mechanisms, all major diagnostic methods, a full comparison of offline sampling versus online monitoring, global application cases, and expert guidance for selecting the right DGA solution.

Table of Contents

  1. What Is Transformer Dissolved Gas Analysis (DGA)?
  2. Fault Gas Generation Mechanisms Inside Transformers
  3. Working Principle of Oil Gas Chromatography
  4. Key Fault Gases and Their Diagnostic Significance
  5. DGA Fault Diagnosis Methods
  6. International Standards and Gas Concentration Thresholds
  7. Online DGA Monitoring Systems
  8. Offline Sampling vs. Online Monitoring — Full Comparison
  9. Global Application Cases
  10. DGA Data Trending and Maintenance Decision-Making
  11. Get a Customized DGA Monitoring Solution
  12. Frequently Asked Questions (FAQ)
  13. Disclaimer

1. What Is Transformer Dissolved Gas Analysis (DGA)?

Dissolved gas analysis (DGA) is a diagnostic technique used to evaluate the internal condition of oil-filled power transformers by analyzing the types and concentrations of gases dissolved in the insulating oil. When electrical or thermal faults occur inside a transformer, the insulating oil and cellulose paper decompose under the influence of abnormal energy, producing specific gases. These gases dissolve in the oil and can be extracted and measured using gas chromatography.

DGA has been used by the global power industry for over five decades and remains the single most important and cost-effective tool for early detection of transformer internal faults. Unlike external inspections or electrical tests that can only detect faults after they have developed to a significant level, DGA can identify incipient faults — including localized overheating, low-energy discharges, and partial discharge activity — long before they escalate into catastrophic failures. This early warning capability makes DGA an indispensable component of any transformer condition monitoring and asset management program.

2. Fault Gas Generation Mechanisms Inside TransformersDissolved Gas Analysis Online Monitor

2.1 Thermal Fault Gas Generation

When a localized thermal fault occurs inside a transformer — such as a hot joint on a connection lead, circulating currents in the core, or overheated insulation — the elevated temperature causes the hydrocarbon molecules in the mineral insulating oil to decompose through a process known as thermal cracking (pyrolysis). The specific gases produced and their relative proportions depend on the severity of the overheating. At lower temperatures (below approximately 300°C), methane (CH₄) and ethane (C₂H₆) are the dominant gases. As the fault temperature increases above 700°C, ethylene (C₂H₄) becomes the primary indicator. Thermal decomposition of cellulose insulation produces carbon monoxide (CO) and carbon dioxide (CO₂).

2.2 Electrical Fault Gas Generation

Electrical faults such as partial discharge (corona), spark discharge, and high-energy arcing produce gases through the electrical dissociation of oil molecules. Low-energy discharges, including partial discharge and corona activity, primarily generate hydrogen (H₂) with smaller quantities of methane. High-energy arcing produces significant quantities of both hydrogen (H₂) and acetylene (C₂H₂). Acetylene is a particularly critical diagnostic gas because it is almost exclusively produced by electrical arcing at temperatures exceeding 1000°C, and even trace amounts indicate severe electrical fault activity.

2.3 Characteristic Gas-to-Fault Correspondence

The relationship between fault types and their characteristic gases can be summarized as follows. Partial discharge and low-energy corona predominantly produce hydrogen. Low-temperature thermal faults (below 300°C) generate methane and ethane. Medium-temperature thermal faults (300–700°C) produce ethylene as the dominant gas. High-temperature thermal faults (above 700°C) generate ethylene in large quantities along with methane. High-energy electrical arcing produces acetylene and hydrogen. Cellulose (paper insulation) degradation produces carbon monoxide and carbon dioxide. Understanding these gas-fault relationships is the foundation of all DGA diagnostic interpretation.

3. Working Principle of Oil Gas Chromatography

Transformer Oil Chromatography DGA Online Monitoring System

3.1 Basic Structure of a Gas Chromatograph

A gas chromatograph (GC) is the core analytical instrument used for DGA. The essential components of a gas chromatograph include a carrier gas supply (typically high-purity nitrogen, helium, or argon), a sample injection system, a chromatographic separation column, a detector, and a data processing system. The separation column — packed or capillary type — uses a stationary phase to separate the dissolved gas mixture into individual components based on their different retention characteristics. Detectors commonly used in oil chromatography for DGA include the thermal conductivity detector (TCD) for hydrogen and the flame ionization detector (FID) for hydrocarbon gases. Some systems also incorporate a methanizer to convert CO and CO₂ into methane for detection by the FID, improving sensitivity.

3.2 Detection Process: From Oil Sampling to Report

The standard DGA process begins with collecting a representative oil sample from the transformer using a gas-tight syringe or sealed sampling container, following the procedures specified in IEC 60567. The dissolved gases are then extracted from the oil sample using one of several degassing techniques — vacuum extraction, headspace equilibrium, or stripping methods. The extracted gas mixture is injected into the gas chromatograph, where the separation column resolves the mixture into individual gas components. Each gas passes through the detector at a characteristic retention time, producing a chromatogram. The data processing system identifies each gas peak and calculates its concentration in parts per million (ppm) by volume in oil. The final analytical report presents the concentration of each dissolved gas, which is then interpreted using established diagnostic methods.

4. Key Fault Gases and Their Diagnostic Significance

4.1 Hydrogen (H₂)

Hydrogen is produced by all types of electrical and thermal faults in transformer oil. It is the predominant gas generated by partial discharge (corona) activity and low-energy electrical discharges. Elevated hydrogen levels with no significant hydrocarbon gases may indicate corona discharge or electrolysis of moisture in the oil. Because hydrogen is generated by nearly all fault types, its presence alone does not pinpoint a specific fault, but a rapid increase in hydrogen concentration is always a cause for further investigation.

4.2 Methane (CH₄)

Methane is primarily associated with low-temperature thermal decomposition of oil, typically in the range of 150–300°C. It may also be produced in smaller quantities by low-energy electrical discharges. Elevated methane concentrations, especially when accompanied by ethane, suggest a low-grade thermal fault such as a bad contact with moderate overheating.

4.3 Ethane (C₂H₆)

Ethane is a characteristic indicator of low-to-moderate temperature thermal faults in the 200–400°C range. It is produced during the early stages of oil thermal degradation. When ethane is the dominant hydrocarbon gas, the fault temperature is generally in the lower thermal range, and the condition may be relatively stable if concentrations are not rising rapidly.

4.4 Ethylene (C₂H₄)

Ethylene is the principal indicator of high-temperature thermal faults, typically above 500°C. Significant ethylene generation indicates severe overheating of oil — often caused by hot metal surfaces in contact with oil, such as overheated connections, circulating currents in the core or tank, or damaged core insulation. When ethylene is the dominant gas, the fault temperature is generally above 700°C, which represents a serious condition requiring prompt attention.

4.5 Acetylene (C₂H₂)

Acetylene is the most critical diagnostic gas in DGA. It is produced almost exclusively by high-energy electrical arcing at temperatures exceeding 1000°C. Even very small concentrations of acetylene (a few ppm) are highly significant and may indicate active arcing between windings, between a winding and the core, or across damaged insulation. The detection of acetylene always warrants urgent investigation and may require immediate load reduction or de-energization of the transformer.

4.6 Carbon Monoxide (CO) and Carbon Dioxide (CO₂)

Carbon monoxide and carbon dioxide are generated by the thermal degradation of cellulose insulation (paper and pressboard). Elevated CO and CO₂ levels — and particularly an increasing CO₂/CO ratio — indicate that the solid insulation is being thermally stressed. A CO₂/CO ratio below 3 may suggest a thermal fault involving the paper insulation, while a ratio above 10 is generally considered normal aging. These gases are also evaluated together with the hydrocarbon gases to distinguish between oil faults and paper insulation faults.

5. DGA Fault Diagnosis Methods

5.1 Key Gas Method

The Key Gas Method, described in IEEE Std C57.104, is the simplest and most intuitive diagnostic approach. It identifies the single gas or group of gases present at the highest concentration or with the most significant rate of increase, and associates that gas with a probable fault type. For example, if hydrogen is the dominant gas, partial discharge is suspected. If ethylene dominates, a high-temperature thermal fault is indicated. If acetylene is present, arcing is the likely cause. While straightforward, this method works best as an initial screening tool and is most effective when combined with other diagnostic techniques for confirmation.

5.2 IEC 60599 Three-Ratio Method

The IEC 60599 three-ratio method uses three specific gas concentration ratios — C₂H₂/C₂H₄, CH₄/H₂, and C₂H₄/C₂H₆ — to classify the fault type into one of several categories: partial discharge (PD), discharges of low energy (D1), discharges of high energy (D2), thermal faults below 300°C (T1), thermal faults between 300–700°C (T2), and thermal faults above 700°C (T3). Each ratio value is coded and the combination of codes maps to a specific fault type in a diagnostic table. This method is widely adopted internationally and provides systematic, repeatable fault classification.

5.3 Duval Triangle Method

The Duval Triangle, developed by Dr. Michel Duval, is one of the most reliable and widely validated DGA diagnostic tools available. It uses the relative concentrations of three gases — methane (CH₄), ethylene (C₂H₄), and acetylene (C₂H₂) — plotted as percentages on a triangular coordinate system. The position of the plotted point within the triangle maps to a specific fault zone: PD (partial discharge), T1, T2, T3 (thermal faults of increasing severity), D1 (low-energy discharge), D2 (high-energy discharge), and DT (mixed thermal and electrical fault). The Duval Triangle has been validated against thousands of actual transformer fault cases worldwide and is recognized for its high diagnostic accuracy. Extended versions — Duval Triangle 4 and Triangle 5 — have been developed for specific applications including low-temperature faults and on-load tap changer diagnostics.

5.4 Rogers Ratio Method

The Rogers Ratio Method is an earlier ratio-based technique that uses four gas ratios — CH₄/H₂, C₂H₆/CH₄, C₂H₄/C₂H₆, and C₂H₂/C₂H₄ — to classify faults. Each ratio is assigned a code based on its value range, and the combination of codes is referenced against a diagnostic table to determine the fault type. While historically significant and still referenced in some utility practices, the Rogers method has largely been superseded by the IEC 60599 ratio method and the Duval Triangle due to its higher rate of unresolvable code combinations.

6. International Standards and Gas Concentration Thresholds

Several international standards provide gas concentration thresholds and diagnostic guidance for DGA. IEEE Std C57.104 (revised 2019) defines a four-condition classification system (Condition 1 through Condition 4) based on individual gas concentrations and total dissolved combustible gas (TDCG) levels. Condition 1 represents normal operation; Condition 4 indicates an active fault requiring immediate action. IEC 60599 provides typical gas concentration values observed in normally operating transformers and establishes the three-ratio diagnostic framework. CIGRE Technical Brochure 771 offers updated guidance on DGA interpretation, including typical values for different transformer types and voltage classes. The following representative threshold values (in ppm) from IEEE C57.104 are commonly referenced for oil-filled transformers: H₂ (100), CH₄ (120), C₂H₆ (65), C₂H₄ (50), C₂H₂ (1), CO (350), CO₂ (2500), and TDCG (720) as Condition 1 upper limits. Values exceeding these thresholds warrant increased monitoring frequency and further evaluation.

7. Online DGA Monitoring Systems

Transformer oil dissolved gas online analysis system

7.1 Why Online Monitoring Is Needed

Conventional laboratory DGA relies on periodic manual oil sampling — typically once every 6 to 12 months for routine monitoring, or quarterly for transformers under observation. This approach has inherent limitations. A fast-developing fault can progress from inception to failure between sampling intervals, leaving no opportunity for early intervention. Manual sampling also introduces risks of sample contamination, gas loss during transport, and human error. Online DGA monitoring eliminates these gaps by providing continuous, automated dissolved gas analysis at intervals as frequent as every few hours, enabling real-time detection of developing faults and immediate alarm notification.

7.2 Composition of an Online Oil Chromatograph Monitoring System

Oil Gas Chromatograph Unit

The online oil gas chromatograph is the central analytical component. It automatically extracts dissolved gases from the transformer oil, separates them through a chromatographic column, and measures their concentrations using integrated TCD and FID detectors. The unit operates on an automated cycle — typically programmable from 1 to 24 hours — and requires no manual intervention for routine operation.

Oil Sampling and Circulation Module

The oil sampling module draws a continuous or periodic oil sample from the transformer through a dedicated sampling valve. A precision oil circulation system ensures that a representative, fresh oil sample reaches the chromatograph for each analysis cycle. Oil is returned to the transformer after analysis, maintaining a closed-loop system with no oil loss.

Gas Extraction Unit

The gas extraction unit separates the dissolved gases from the oil sample using vacuum degassing, membrane permeation, or headspace equilibrium techniques. The choice of extraction method affects the system’s sensitivity, response time, and maintenance requirements. Vacuum degassing and headspace methods are the most common in modern online DGA monitors.

Control and Data Processing Module

An embedded industrial controller manages the entire analysis cycle, processes the chromatographic data, calculates gas concentrations, evaluates diagnostic ratios, and generates alarm outputs. Data is stored locally and transmitted to external systems via communication interfaces.

Communication Interface

The online DGA monitoring system provides RS485 (Modbus RTU) as the standard communication interface for integration with substation SCADA systems, DCS platforms, and transformer monitoring IEDs. Optional interfaces include Ethernet (Modbus TCP/IP), IEC 61850, and DNP3.0 to meet specific utility communication architecture requirements.

7.3 Key Technical Parameters

A typical online oil chromatograph monitoring system measures all seven key gases: H₂, CH₄, C₂H₆, C₂H₄, C₂H₂, CO, and CO₂. Measurement accuracy is typically ±5% of reading or ±2 ppm (whichever is greater) for hydrocarbon gases and ±10% for CO and CO₂. The detection limit is generally 0.5–2 ppm for hydrocarbon gases and 5–10 ppm for CO/CO₂. The analysis cycle time ranges from 30 minutes to 4 hours depending on the configuration. Operating temperature range is typically −40°C to +55°C for outdoor installation. The system is designed for unattended operation with a maintenance interval of 12 months or longer.

7.4 SCADA Integration and Alarm Logic

The online DGA monitor transmits real-time gas concentration data, TDCG values, gas generation rate (ppm/day), and diagnostic fault codes to the SCADA system. Configurable alarm thresholds can be set for individual gas concentrations, total combustible gas, and rate-of-change values. Multi-level alarm outputs (pre-alarm, alarm, urgent alarm) enable graduated response actions — from increased monitoring frequency to immediate operator notification and automatic protective actions.

8. Offline Sampling vs. Online Monitoring — Full Comparison

Parameter Offline Laboratory DGA Online DGA Monitoring System
Sampling Method Manual oil sampling by technician Automatic, continuous oil circulation
Analysis Frequency Quarterly to annually Every 30 minutes to 4 hours (configurable)
Fault Detection Speed Days to months (depends on sampling schedule) Near real-time (within one analysis cycle)
Sample Contamination Risk Moderate (handling, transport, storage) Minimal (closed-loop system)
Gas Measurement All 7 key gases + additional gases All 7 key gases (H₂, CH₄, C₂H₆, C₂H₄, C₂H₂, CO, CO₂)
Accuracy ±5–10% (lab dependent) ±5% of reading or ±2 ppm
Rate-of-Change Tracking Limited (insufficient data points) Continuous trend and generation rate (ppm/day)
Labor Requirement High (sampling crew, lab technician) Minimal (periodic calibration and maintenance)
SCADA Integration Not applicable RS485, Modbus RTU/TCP, IEC 61850, DNP3.0
Alarm Capability None (report-based only) Multi-level automatic alarms
Maintenance Interval N/A 12 months or longer
Initial Cost Low (per-sample lab fee) Medium–High (equipment investment)
Long-Term Cost Cumulative (labor + lab fees over years) Lower per data point over service life
Best Suited For Routine monitoring, lower-criticality units Critical transformers, high-value assets, remote sites

As the comparison shows, online DGA monitoring systems offer decisive advantages in detection speed, data continuity, and automation for critical transformer assets. Offline laboratory DGA remains valuable as a complementary verification tool and for routine fleet monitoring of lower-risk units.

9. Global Application Cases

9.1 High-Voltage Power Transformers (110 kV – 220 kV)

Online oil chromatograph monitoring systems have been widely deployed on 110 kV and 220 kV utility power transformers across substations in Asia, the Middle East, Africa, and South America. In these installations, the continuous DGA data stream enabled operators to detect early-stage thermal faults — such as overheated tap changer contacts and circulating currents — weeks before they would have been identified by routine periodic sampling. Several utilities reported that early fault detection facilitated planned maintenance interventions, avoiding unplanned outages and preventing potential transformer failures.

9.2 Ultra-High-Voltage Transmission Transformers (500 kV and Above)

UHV transformers represent extremely high-value assets where a single failure can result in millions of dollars in direct damage and grid disruption. Online DGA monitors installed on 500 kV and 750 kV transmission transformers provide continuous gas trending data that enables operators to track the health of these critical units in real time. The fast analysis cycle ensures that rapidly developing faults — particularly arcing events indicated by sudden acetylene generation — are detected within hours rather than months.

9.3 Industrial Power Transformers

In industrial settings such as steel mills, chemical plants, and mining operations, transformers are often subjected to severe and highly variable loading profiles. Online DGA monitoring is particularly valuable in these environments because the dynamic thermal stress increases the likelihood of incipient faults. Continuous dissolved gas tracking allows maintenance teams to correlate gas generation events with specific loading conditions, enabling targeted root-cause analysis and optimized maintenance scheduling.

9.4 Offshore Wind Farms and Remote Sites

Transformers at offshore wind farms, remote hydroelectric stations, and desert substations are often difficult and expensive to access for routine oil sampling. Online DGA monitoring systems with remote SCADA integration eliminate the need for physical site visits for dissolved gas data collection. Operators can monitor transformer health from a centralized control room, receive automatic alarms for abnormal gas levels, and dispatch maintenance crews only when actionable conditions are detected — significantly reducing operational costs and improving asset reliability in remote locations.

10. DGA Data Trending and Maintenance Decision-Making

Individual DGA snapshots provide useful information, but the true power of dissolved gas analysis lies in trend analysis over time. A single gas concentration reading must be evaluated in context — what matters most is whether gas levels are stable, increasing slowly, or rising rapidly. The gas generation rate (expressed in ppm per day or ppm per month) is a more powerful diagnostic indicator than the absolute concentration alone. A transformer with moderate gas levels that are stable may be operating safely with a known, inactive condition. Conversely, a transformer with lower absolute gas levels but a sharply increasing trend may be developing an active fault that requires urgent investigation.

Online DGA monitoring systems excel at providing the continuous data density needed for reliable trend analysis. With data points collected every few hours, the gas generation rate can be calculated with high confidence, and short-duration transient gassing events can be captured that would be completely missed by quarterly manual sampling. By integrating DGA trend data with other monitoring parameters — such as winding temperature, load current, and oil quality — maintenance engineers can make informed, condition-based decisions about inspection timing, loading limits, and repair scheduling, transitioning from time-based maintenance to true predictive maintenance.

11. Get a Customized DGA Monitoring Solution

Every transformer application presents unique requirements for DGA monitoring — from the number of units to be monitored and the desired analysis cycle frequency, to the specific communication protocols and environmental conditions. Our engineering team at FJINNO provides tailored online DGA monitoring solutions for transformer manufacturers, electric utilities, and industrial operators worldwide.

Whether you need a single-unit online oil chromatograph for a critical substation transformer or a fleet-wide monitoring deployment with centralized data management, we deliver fully customized system configurations with complete technical support, commissioning assistance, and after-sales service.

Contact us today to discuss your project requirements, request a quotation, or schedule a technical consultation. Visit www.fjinno.net for more information.

12. Frequently Asked Questions (FAQ)

Q1: What gases does DGA measure in transformer oil?

Standard DGA measures seven key gases dissolved in transformer insulating oil: hydrogen (H₂), methane (CH₄), ethane (C₂H₆), ethylene (C₂H₄), acetylene (C₂H₂), carbon monoxide (CO), and carbon dioxide (CO₂). Some laboratories also measure oxygen and nitrogen to assess oil handling quality and sealed system integrity.

Q2: What does the presence of acetylene in transformer oil indicate?

Acetylene (C₂H₂) is generated almost exclusively by high-energy electrical arcing at temperatures exceeding 1000°C. Even trace amounts of acetylene — as low as 1–2 ppm — are considered highly significant and may indicate active arcing inside the transformer. Detection of acetylene always warrants urgent investigation and potentially immediate protective action.

Q3: How often should offline DGA sampling be performed?

For routine monitoring, most international standards and utility practices recommend annual DGA sampling for transformers in normal service. Quarterly sampling is recommended for transformers under observation or with elevated gas levels. Monthly or more frequent sampling may be required for transformers with known or suspected active faults. Online DGA monitoring can supplement or replace periodic manual sampling for critical assets.

Q4: What is the Duval Triangle and how does it work?

The Duval Triangle is a graphical diagnostic method that uses the relative percentages of three gases — methane, ethylene, and acetylene — plotted on a triangular coordinate system. The position of the data point within the triangle maps to a specific fault zone (PD, T1, T2, T3, D1, D2, or DT). It is one of the most reliable DGA diagnostic tools, validated against thousands of actual transformer fault cases worldwide.

Q5: What is the difference between the IEC 60599 ratio method and the Rogers ratio method?

Both methods use gas concentration ratios to classify fault types, but they differ in the number and selection of ratios used. The IEC 60599 method uses three ratios (C₂H₂/C₂H₄, CH₄/H₂, C₂H₄/C₂H₆) and is the current international standard. The Rogers method uses four ratios and has a higher rate of unresolvable code combinations. The IEC method is generally preferred in modern practice.

Q6: Can an online DGA monitor detect all the same gases as a laboratory analysis?

Yes. Modern online oil chromatograph systems measure all seven key dissolved gases (H₂, CH₄, C₂H₆, C₂H₄, C₂H₂, CO, CO₂) with accuracy comparable to laboratory methods. Some simpler online monitors measure only hydrogen or a subset of gases, so it is important to select a full multi-gas online chromatograph for comprehensive DGA monitoring.

Q7: What communication protocols do online DGA systems support?

Standard communication is RS485 with Modbus RTU protocol. Many systems also support Ethernet with Modbus TCP/IP, IEC 61850 for digital substation architectures, and DNP3.0. The specific protocol can be configured to match the substation SCADA or DCS communication requirements.

Q8: How does temperature affect dissolved gas concentrations in transformer oil?

Oil temperature influences gas solubility — higher oil temperatures reduce the solubility of gases in oil, potentially causing dissolved gases to migrate into the gas space (Buchholz relay area). Temperature also affects gas generation rates from active faults. Online DGA systems typically include oil temperature measurement to compensate for solubility effects and normalize readings for accurate trending.

Q9: What maintenance does an online DGA monitor require?

Most online oil chromatograph systems are designed for 12 months or longer between maintenance intervals. Routine maintenance typically includes calibration gas verification, carrier gas cylinder replacement (if applicable), oil sampling line inspection, and detector performance check. Some systems use carrier-gas-free designs to further reduce maintenance requirements.

Q10: How do I determine whether my transformer needs online DGA monitoring?

Online DGA monitoring is most beneficial for high-value, high-criticality transformers where an unplanned failure would result in significant financial loss, safety risk, or grid reliability impact. This includes large power transformers at major substations, generator step-up transformers, interconnection transformers, and transformers at remote or difficult-to-access locations. Our engineering team can help you assess your fleet and identify the units that would benefit most from continuous monitoring. Contact us at www.fjinno.net for a consultation.

13. Disclaimer

The information provided in this article is intended for general educational and reference purposes only. While every effort has been made to ensure the accuracy and reliability of the content at the time of publication, FJINNO makes no warranties or representations, express or implied, regarding the completeness, accuracy, or suitability of the information for any specific application. Transformer dissolved gas analysis, diagnostic interpretation, and maintenance decisions must be carried out by qualified engineers in accordance with applicable international standards, local regulations, and established engineering best practices. Readers are advised to consult the latest editions of IEC 60599, IEEE Std C57.104, and other relevant standards before making any operational or purchasing decisions based on DGA data. FJINNO shall not be liable for any direct, indirect, or consequential damages arising from the use of or reliance on the information presented in this article. For project-specific technical guidance, please contact our engineering team at www.fjinno.net.