The Energy Storage Transformer Monitoring Device is designed for temperature monitoring, alarm control, cooling fan control and operating-status supervision of transformers used in energy storage power systems. It provides continuous transformer winding temperature monitoring and can be configured with additional functions including ambient temperature, transformer core temperature, ambient humidity and cooling fan fault detection.
Optional 4–20 mA analog output and RS485 communication allow temperature and operating-status data to be transmitted to external monitoring and control systems.
- Transformer winding temperature monitoring
- Automatic cooling fan control
- Overtemperature alarm and trip output
- Historical maximum temperature recording
- Temperature compensation and simulation test
- Optional transformer core temperature monitoring
- Optional ambient temperature and humidity monitoring
- Optional cooling fan fault detection
- Optional 4–20 mA analog output
- Optional RS485 MODBUS-RTU communication
Technical Specifications
| Parameter | Specification |
|---|---|
| Operating Temperature | -25°C to +55°C |
| Operating Humidity | ≤95% RH at 25°C |
| Power Supply | AC 220 V (±10%), 50/60 Hz (±2 Hz); customizable according to project requirements |
| Temperature Measurement Range | -30.0°C to 240.0°C |
| Measurement Accuracy | ±1% FS; controller Class 0.5, sensor Class B |
| Resolution | 0.1°C |
| Cooling Fan Contact Capacity | 6 A / AC 250 V |
| Control Contact Capacity | 5 A / AC 250 V or 5 A / DC 30 V resistive; optional 5 A / DC 220 V |
| Power Consumption | ≤8 W |
| Communication | RS485, MODBUS-RTU optional |
| Analog Output | 4–20 mA optional |
Monitoring and Control Functions
| Function | Description |
|---|---|
| Winding Temperature Monitoring | Continuously monitors transformer winding temperature with 0.1°C resolution. |
| Cooling Fan Control | Automatically starts and stops cooling fans according to configured temperature thresholds. |
| Overtemperature Alarm | Provides relay output when the configured overtemperature alarm threshold is reached. |
| Overtemperature Trip | Provides trip output at the configured high-temperature threshold. |
| Historical Maximum Temperature | Records historical maximum temperature for operating-condition review. |
| Black Box Function | Records temperature values at power loss and stores historical maximum temperature information. |
| Temperature Compensation | Supports temperature measurement compensation within ±19.9°C. |
| Simulation Test | Simulates temperature changes to test fan, alarm, trip and output-contact operation. |
Optional Functions
The Energy Storage Transformer Monitoring Device can be configured according to transformer design and project requirements.
| Option | Function |
|---|---|
| D | Basic configuration |
| E | 4–20 mA analog current output |
| F | RS485 communication |
| G | Ambient temperature measurement |
| I | Transformer core temperature measurement |
| H | Ambient humidity measurement |
| L | Cooling fan fault detection |
Temperature Alarm and Cooling Control
The device provides configurable temperature thresholds for transformer cooling, alarm and trip control. Actual operating values can be configured according to transformer requirements and factory settings.
| Control Function | Factory Default |
|---|---|
| Cooling Fan Stop | 80.0°C |
| Cooling Fan Start | 100.0°C |
| Overtemperature Alarm | 130.0°C |
| Overtemperature Trip | 150.0°C |
| Core Overtemperature Alarm | 130.0°C |
| Core Overtemperature Trip | 150.0°C |
| Humidity-Controlled Heater Start | 65% RH |
Note: Alarm, cooling and trip thresholds may vary according to the ordered configuration and factory settings.
RS485 MODBUS-RTU Communication
Models equipped with the RS485 communication function use the MODBUS-RTU protocol. Communication address, parity and baud rate can be configured through the device interface.
| Communication Item | Specification |
|---|---|
| Interface | RS485 |
| Protocol | MODBUS-RTU |
| Data Length | 8 bits |
| Parity | 0 / 1 / 2 |
| Stop Bit | 1 |
| Minimum Sampling Interval | 500 ms |
Depending on the ordered configuration, MODBUS registers can provide winding temperature, ambient temperature, transformer core temperature, relay status and historical maximum temperature data.
4–20 mA Temperature Output
The optional analog output provides a linear 4–20 mA signal corresponding to a temperature range of 0–200°C. The output can be connected directly to an analog input module of a compatible monitoring or DCS system for temperature acquisition, display and control.
| Analog Output | Corresponding Temperature |
|---|---|
| 4 mA | 0°C |
| 20 mA | 200°C |
A 250 Ω precision resistor can be connected to the current output when a 1–5 V voltage signal is required.
Typical Applications
- Battery energy storage system transformers
- Energy storage power station transformers
- Energy storage step-up transformers
- Transformer cabinets with forced-air cooling
- Transformer temperature monitoring and cooling control
- Remote transformer monitoring through RS485 communication
Standards and Quality Management
| Item | Standard |
|---|---|
| Product Standard | JB/T 7631-2016 |
| EMC Test | IEC 61000-4:2005 |
| EMC Test | GB/T 17626-2008 |
| Quality Management | ISO 9001:2015 |
| Environmental Management | ISO 14001:2015 |
| Occupational Health and Safety | ISO 45001:2018 |
FAQ
What does the Energy Storage Transformer Monitoring Device monitor?
The standard configuration monitors transformer winding temperature. Depending on the selected configuration, the device can also monitor ambient temperature, transformer core temperature, ambient humidity, cooling fan operation and related alarm conditions.
Can the device automatically control transformer cooling fans?
Yes. The device supports configurable fan start and stop temperature thresholds and provides relay contacts for automatic cooling fan control.
Does it provide overtemperature alarm and trip outputs?
Yes. Separate overtemperature alarm and high-temperature trip thresholds can be configured, with corresponding relay outputs for transformer protection and control.
Does the device support RS485 communication?
Yes. Optional RS485 communication supports MODBUS-RTU and can transmit transformer temperature and operating-status information to compatible monitoring systems.
Is 4–20 mA temperature output available?
Yes. The optional 4–20 mA output corresponds to a temperature range of 0–200°C and can be connected to compatible analog input modules or DCS systems.
Can transformer core temperature be monitored?
Yes. Transformer core temperature measurement is available as an optional function and can be combined with configurable core overtemperature alarm and trip settings.
Can the device detect cooling fan faults?
Yes. Cooling fan fault detection is available as an optional function and detects abnormal fan operating current according to configured thresholds.
Can the configuration be customized for different transformer projects?
Yes. The standard power supply is AC 220 V, and the manual specifies that power supply and functional configurations can be selected according to project requirements and the actual order.
Configure Your Energy Storage Transformer Monitoring Device
Different energy storage transformer projects may require different combinations of winding temperature monitoring, transformer core temperature monitoring, cooling control, alarm outputs, RS485 communication, 4–20 mA output, humidity monitoring and cooling fan fault detection. INNO can configure the monitoring device according to transformer design and project interface requirements.