The YN-XP502F-3T is an intelligent temperature monitoring system designed specifically as a dry type transformer temperature controller. As a dedicated transformer monitor, this thermostat is specially customized for dry-type transformer applications: the thermostat is an embedded installation with strong anti-disturbance ability. It has unique technical advantages in temperature measurement under special environments such as high voltage and strong electromagnetic interference, and has reliable EMC and EMI performance. It has the characteristics of large output contact capacity, complete function, color LCD display interface with pictures and texts, etc., and is simple to set and easy to operate.
Manufactured by Fuzhou Innovation Electronic Scie&Tech Co., Ltd., this dry type transformer temperature indicator combines precise multi-channel temperature monitoring with an intuitive touchscreen interface, making it a reliable choice for substations, distribution rooms and industrial power systems that demand continuous, accurate temperature monitoring.

Product Features
| Feature | Description |
|---|---|
| 3-Channel PT100 Temperature Sensor Input | 3-channel PT100 temperature measurement: 3-channel winding temperature measurement, and 1 channel for core temperature measurement |
| Color Touch Display | Equipped with 2.8-inch color LCD touch screen |
| Stable Processing Core | Utilize a CPU based on the ARM architecture, renowned for its robust data processing capabilities and system stability |
| Modular Circuit Design | The circuit board design philosophy adopts a modular approach, with a clear separation of strong and weak currents to prevent spatial crosstalk |
| Remote Monitoring Ready | Standard MODBUS-RTU communication protocol for seamless integration into a broader transformer monitoring system |
Basic Technical Parameters
| Item | Parameter |
|---|---|
| Working environment | Ambient temperature: -25℃ ~ +55℃; Ambient humidity: ≤95%(25℃) |
| Working power supply | AC/DC 24~240V |
| Working frequency | 50Hz or 60Hz(±2Hz) |
| Measurement range | -30.0℃ ~ 240.0℃ |
| Measurement accuracy | ±1%FS(thermostat level of 0.5 class, sensor of B class) |
| Resolution | 0.1℃ |
| Fan contact capacity | 16A/250VAC |
| Power | ≤10W |
| Installation | Embedded installation |
| Overall dimension | 96×96×84mm (L×W×H) |
| Opening size | 90×90mm (L×W) |
| Communication protocol | Standard MODBUS-RTU (Address 1~247, Baud rate 1200~38400, default 9600) |
Standards & Certifications
Production standard: JB/T7631-2016 《Electronic thermostat for Transformers》 Industry standards.
Certification standards: ISO9001:2015 International Quality Management System certification; ISO14001:2015 Environmental Management System Certification; ISO45001:2018 Occupational Health And Safety Management System Certification.
Test standards: IEC61000-4:2005 International Standards; GB/T17626-2008 《Electromagnetic Compatibility Test And Measurement Technology》 Standard.
Liquid Crystal Display Interface
After the initialization process is completed, this transformer monitor automatically proceeds to the “Main Interface,” and upon successful connection, it automatically reads the temperature. The display interface refreshes the temperature information every 1000ms, giving operators a live view of the temperature monitoring system at all times.
Temperature Display Area

The main interface simultaneously displays real-time readings from CH1, CH2 and CH3, with distinct color coding for different operating states so that abnormal conditions can be identified at a glance:
| Display information | Normal display status | Temperature controller failure | Sensor broken line | Over-temperature alarm | Over-temperature trip |
|---|---|---|---|---|---|
| Content | 45.5 | -ER- | -OP- | 130.0 | 152.0 |
When a device failure occurs (temperature exceeding the upper and lower limits of the temperature controller), the screen displays -ER-. When the sensor is in an open circuit condition, the screen displays -OP-. The buzzer sounds an alarm whenever any of the above states occur; when an alarm is triggered, the mute button will flash, and pressing it will cancel the buzzer alarm.
Clock Display Area

The real-time clock is shown at the top of the main screen. Tapping this area opens the clock settings, allowing adjustment of year, month, day, hour, minute and second. A built-in clock battery keeps the clock running accurately even when the thermostat loses power, ensuring reliable time-stamped records for the monitoring system.
Function Status Indicator Area

| Status name | Fan operation | Winding alarm | Winding trip | Device failure |
|---|---|---|---|---|
| Description | Indicator lights when the fan is running | Indicator lights during a winding over-temperature alarm | Indicator lights during a winding over-temperature trip | Indicator lights when the device itself fails |
Key Region
| Key | Function |
|---|---|
| Set key | Opens a password input window; enter the correct password (default 13) to access the parameter setting menu |
| Historical Data key | Opens the historical data window to review past temperature records and historical highs |
| Language toggle key | Opens the language selection interface |
| Manual Fan key | Manually starts the fan; the icon background turns green once activated |
| Alarm mute button | Silences the buzzer alarm |
Applications
As a dependable temperature monitoring system, the YN-XP502F-3T dry type transformer temperature sensor and controller is widely used in substations, industrial distribution rooms and box-type substations for continuous transformer monitor duties. It helps operators track winding temperature in real time, issue early warnings before overheating occurs, and coordinate fan operation automatically — reducing the risk of outages and equipment damage caused by transformer overheating.
A Cost-Effective Alternative to European Imports
Long dominated by manufacturers from Italy, Turkey and other European countries, the dry type transformer temperature monitoring market has relied heavily on imported control units — often meaning longer lead times, higher costs and slower after-sales support. YN-XP502F-3T delivers the same core protection performance your project needs, built and supported locally.
- Faster delivery — no overseas shipping or customs delays
- Lower total cost — competitive pricing without compromising reliability
- Responsive support — direct access to our engineering team, no waiting on overseas agents
- Flexible customization — channel count, alarm thresholds and communication settings tailored to your project
Looking to replace an imported temperature controller on your next project? Contact us for a side-by-side comparison and full technical documentation →