- Record the existing WTI model, temperature range, sensing arrangement and terminal wiring.
- Confirm alarm, trip and cooling-control contact requirements before selecting a replacement.
- Check power supply, output signals and communication interfaces.
- Verify panel dimensions, mounting method and terminal compatibility.
- Confirm whether the existing temperature sensing system can be reused.
- Match the replacement instrument to the transformer protection and cooling logic.
- Verify all alarm, trip and cooling functions after installation.
Replacement selection should begin by confirming how the existing transformer winding temperature indicator interacts with the transformer sensing, cooling and protection circuits. Reading the right temperature is not enough: a replacement that closes the wrong contact, needs a supply the panel cannot provide or misses the mounting cutout turns a simple swap into a protection problem.
Planning a 2027 outage or spares purchase? Sections below cover the checks that decide whether a new WTI will fit, from model matching and contact logic to panel dimensions and commissioning. Examples refer to oil-immersed transformers fitted with load-current simulation WTIs, including BWR-series instruments.
Table of Contents
- 1. What to Check Before Replacing a Transformer WTI
- 2. Transformer Winding Temperature Indicator Compatibility
- 3. Temperature Range and Sensor Compatibility
- 4. Alarm, Trip and Cooling Control Contacts
- 5. Power Supply, Outputs and Communication
- 6. Mechanical and Panel Compatibility
- 7. Replacing BWR Winding Temperature Indicator Models
- 8. WTI Replacement Procedure
- 9. Direct Replacement or Upgrade?
- 10. Replacement Checklist
- Frequently Asked Questions
What to Check Before Replacing a Transformer Winding Temperature Indicator

Transformer winding temperature indicator replacement starts from the existing instrument, not from the new model catalog. Everything the replacement must work with, including temperature range, contact logic, wiring and panel opening, is defined by the old unit, so document it completely before shortlisting any model.
Record the following from the nameplate, the terminal diagram and the transformer drawings:
- Manufacturer and full model number, including suffix letters and any special-environment code
- Temperature range printed on the dial
- Sensor input: bulb and capillary length, compound transmitter, CT input or Pt100 signal
- Power supply voltage and frequency, where the instrument or its remote display has one
- Terminal diagram and wire numbering
- Alarm, trip and cooling contacts: how many are wired and what each one switches
- Analog output or communication link, if connected to a panel or SCADA
- Panel cutout, mounting method and rear clearance
Photographs of the nameplate, dial, terminals and transmitter make model matching far more reliable than a verbal description.
Confirm first that the instrument is a WTI and not an oil temperature indicator. On most oil-immersed units both gauges are installed together and look similar, yet the WTI vs OTI difference is fundamental: the WTI receives a CT signal that heats the sensing element, while the OTI reads top-oil temperature only. Ordering an OTI for a WTI position removes the load-dependent winding indication entirely.
Transformer Winding Temperature Indicator Compatibility
WTI replacement does not require an identical model number, but every function the transformer relies on must be compatible, both electrically and mechanically. Comparing old and new instruments line by line exposes mismatches before the order is placed.
| Item | Existing WTI | Replacement WTI | Why It Must Match |
|---|---|---|---|
| Temperature range | Dial scale and any special scale marks | Scale that covers every set point with margin | Set points near or beyond the end of the scale cannot be set or read reliably |
| Sensor / input method | Bulb and capillary, compound transmitter, CT input or Pt100 signal | Same sensing principle and a compatible CT input | Winding temperature is simulated from oil temperature plus load current, so a different method changes what the dial indicates |
| Power supply | Supply voltage and frequency, if any | Same supply, or one the panel can provide | An unavailable supply leaves the display, output or signal electronics inactive |
| Alarm contacts | Number wired and the temperature each closes at | At least as many, each rated for its circuit | Alarm contacts feed annunciators, PLC inputs or SCADA |
| Trip contacts | Number wired and the circuit they operate | Rated for the trip circuit voltage and current, AC or DC | Trip wiring is the final thermal protection layer |
| Cooling control | Fan or pump stages driven by the WTI | Enough contacts for every stage | A missing contact means a cooling stage never starts |
| Analog output | None, Pt100 or 4-20 mA | Same signal type, or one the receiving device accepts | Receiving inputs are configured for one signal type and span |
| Communication | None, or an RS485 link | Interface and protocol the receiving system supports | A protocol mismatch stops remote data without any visible fault at the instrument |
| Panel dimensions | Cutout, hole pattern and rear depth | Same cutout and depth, or an agreed adaptation | An instrument that does not fit cannot be installed, whatever its electrical match |
| Terminal wiring | Terminal numbers and cable entry | Same layout, or documented rewiring | Changed terminals need updated drawings and a full circuit check |
| Environment | Ambient range, humidity, tropical code | Equal or better ratings | Humid or tropical sites need the matching special-environment code |
Two instruments from the same series can still differ in several rows of this table, so compatibility has to be verified for each model rather than assumed from the series name.
WTI Temperature Range and Sensor Compatibility
Two dials that look identical may not be interchangeable. Selecting the correct WTI and OTI temperature range requires checking the original instrument and transformer design rather than relying on appearance alone. Typical WTI dials are graduated 0-150 °C or 0-160 °C, and the scale must cover every alarm, trip and cooling set point with margin.
Even within one product family the range can differ. BWR2 instruments are specified for 0-160 °C, while the BWR-04J(TH) is supplied as 0-150 °C by default with 0-160 °C as an option. Accuracy class is 1.5 on both, yet the allowable error follows the scale span: ±2.4 °C on 0-160 °C and ±2.25 °C on 0-150 °C.
Sensing Principle and Input Type
Winding temperature indicators do not measure the winding directly. Top-oil temperature is sensed in a thermometer pocket, and a CT-fed heating element adds a load-proportional rise that approximates the winding gradient. Because the indication is simulated rather than measured, the replacement must reproduce the same thermal image. Transformer winding temperature measurement methods differ in what they actually sense, and a direct probe cannot simply stand in for a CT-heated bulb.
Check these items before ordering:
- Input type: bulb and capillary, compound transmitter with Pt100 output, or another arrangement
- CT secondary current: the BWR2 compound transmitter accepts 0.5 A to 5.0 A, so the transformer CT secondary must fall inside that input range
- Heater or gradient setting: it must be matched to the winding-to-oil gradient in the transformer test report, because incorrect heater current makes the indicator read high or low at every load point
- Contact and output logic: which indicated value drives each contact and each output signal
Can the Existing Sensor Be Reused?
Sometimes. Reuse depends on bulb diameter and length, mounting thread, capillary condition and the sensing element type the new instrument expects. Thread is a good example: BWR2 compound transmitters and the BWR-04J(TH) temperature package both use an M27 × 2 mm thread, yet the bulb is Φ18 × 150 mm on the BWR2 and Φ14 × 150 mm on the BWR-04J(TH), so the thermometer pocket fit still has to be checked. Capillaries with kinks, dry pockets and loose bulbs cause lag or offset and are better replaced than reused.
WTI Alarm, Trip and Cooling Control Contacts
Contacts connect the WTI to the rest of the transformer. Depending on model and wiring design, they may drive a high-temperature alarm, fan start and stop, a trip circuit or other cooling control. A replacement transformer winding temperature controller has to offer the same switching capability at the same points in the circuit.
Alarm and trip contacts serve different purposes: the alarm is an early warning that prompts investigation, while the trip is a protective action. Understanding how a transformer over-temperature alarm should be handled on site makes it easier to define what the replacement contacts must preserve.
- Contact quantity: BWR2 instruments have four adjustable switch contacts (K1 to K4), so circuits that use more than four need a different configuration
- Contact rating: BWR2 contacts are rated AC220V/5A and BWR-04J(TH) contacts AC220V/5A and DC220V/3A, so DC trip or cooling circuits need a confirmed DC rating before ordering
- Function assignment: which contact serves the alarm, which serves each cooling stage and which serves the trip
- Switching tolerance: BWR-04J(TH) lists a switching error of ±2 °C, which matters when set points sit close together
Contacts leave the factory at standard positions (K1 50 °C, K2 75 °C, K3 100 °C and K4 120 °C on the BWR2) that serve only as starting points, because function and set point are configured per project. Alarm, trip and fan-start temperatures must follow the transformer nameplate, the manufacturer’s test report and approved site protection logic. They should not be copied from another transformer or a generic table.
The replacement instrument must preserve the transformer protection logic, and any change in contact count, rating or function needs sign-off from whoever owns that logic.
WTI Power Supply, Analog Output and Communication
Older WTIs may use relay contacts only. Newer controllers can add analog signals, digital displays and communication, which brings power supply and signal compatibility into the selection. A communication upgrade does not remove the need to keep the original relay logic working.
Power Supply
Supply requirements are model-specific. The BWR-04J(TH) is specified for AC220 V ±10% at 50-60 Hz. The optional BWX digital display for BWR2 instruments is offered with an AC220V code or a wide-range AC/DC code, while the XMT-22B remote display is standard at AC220V (+10%, -15%) with AC85-250 V or DC110-300 V available when specified at order. Supply values for the BWR2 indicator itself must be confirmed from the existing instrument nameplate and replacement model specification.
Analog Output
BWR2 function codes define the output: A for Pt100 and J for a two-wire 4-20 mA signal. The BWR-04J(TH) provides a 4-20 mA DC signal. The receiving device must accept the same signal type and be scaled to the same temperature span, since an input card configured for Pt100 cannot read a 4-20 mA loop and the reverse is equally true.
RS485 and Remote Display
RS485 communication is available on BWR2 systems through the optional BWX digital display (function code F), with 4-20 mA output as code E and zero, one or two relays selectable. Protocol and register details must be confirmed before integration with PLC or SCADA. Display relays and the instrument’s own switch contacts are separate circuits, so confirm which ones the cooling and trip logic actually uses.
Mechanical and Panel Compatibility for WTI Replacement
Purchasing teams often compare electrical parameters only. Electrical compatibility is not enough if the instrument cannot fit the existing panel, side wall or thermometer pocket, so mechanical checks belong in the same review as contacts and outputs.
- Mounting: BWR2 indicators are fixed vertically on the transformer side wall with three M6 bolts, so the existing hole pattern must be compared with the final dimension drawing
- Terminal location and cable entry: BWR2 instruments use a cable entry hole for a Φ16 plastic-coated hose connector, and 2.5 mm² single-wire conductors are recommended
- Bulb and pocket: bulb diameter and length, M27 × 2 mm thread and pocket depth
- Capillary routing: length is set by the last group of digits in the BWR2 instrument number and is 5 m on the BWR-04J(TH); the run should be fixed about every 300 mm, with surplus length coiled at a diameter above 200 mm
- Remote display: cutout and rear depth, compared in the table below
| Remote Display | Supply | Panel Opening | Overall Size |
|---|---|---|---|
| BWX digital display (Pt100 or 4-20 mA input) | AC220V or AC/DC wide-range, by code | 153 × 77 mm | 160 × 80 × 120 mm |
| XMT-22B digital temperature display regulator | AC220V (+10%, -15%); AC85-250 V or DC110-300 V on order | 76 × 152 mm, +1 mm tolerance (height × width) | 80 × 160 × 100 mm (height × width × depth) |
Cutouts are nearly the same, yet rear depth differs by 20 mm, which matters in shallow cabinets. Final dimension drawings should be confirmed before panel work or site installation.
Replacing BWR Winding Temperature Indicator Models
BWR-series winding temperature indicators may combine local temperature indication with alarm, trip or cooling-control functions depending on the model configuration. Belonging to the same series does not make two models interchangeable. Suffix letters, switch quantity, output type, capillary length and transmitter type all change what the instrument does in the circuit.
Reading the Model Code
BWR2 codes identify the series, a control switch quantity configured by requirement, a function code (A for Pt100 output, J for two-wire 4-20 mA output) and a special-environment code (TH for humid tropical areas, TA for dry tropical areas, T for both). Legacy BWR-04 and BWR-06 families include many suffix variants, such as BWR-04A(TH), BWR-04AJ(TH) and BWR-06J(TH), and each needs to be matched by its complete model string rather than by prefix.
Transformer Temperature Controller Replacement: BWR2 Compared with BWR-04J(TH)
Two FJINNO models show why parameters cannot be mixed. The BWR2 transformer winding temperature indicator and the BWR-04J winding temperature indicator differ in range, output, contact rating and sensor dimensions.
| Model | Temperature Range | Alarm / Trip / Cooling Contacts | Output | Communication | Typical Replacement Use |
|---|---|---|---|---|---|
| BWR2-04J(TH), BWR2-04AJ(TH), BWR2-05J(TH), BWR2-06AJ(TH) | 0-160 °C | 4 adjustable contacts (K1-K4), AC220V/5A; function assigned per project | Pt100 (code A), 4-20 mA two-wire (code J) | RS485 only through the optional BWX display (code F) | Existing BWR2-type indicator with compound transmitter, CT input and switch contacts |
| BWR-04J(TH) | 0-150 °C default; 0-160 °C optional | Quantity —; rated AC220V/5A and DC220V/3A | 4-20 mA DC | — | Existing BWR-04J(TH)-type unit with 4-20 mA output and AC220 V supply |
Operating ambient limits also differ (-40 °C to +65 °C for BWR2, -40 °C to +55 °C for BWR-04J(TH)), as do bulb size (Φ18 × 150 mm and Φ14 × 150 mm). Parameters not published for a given model, such as the contact quantity of the BWR-04J(TH), must be confirmed from the existing instrument nameplate and replacement model specification.
Detailed BWR2-04 and BWR2-06 replacement selection starts with the old model label, wiring diagram and installation photo, which together settle suffix, contact quantity and transmitter type. The BL-F composite transmitter used with these instruments is part of the winding temperature system rather than an optional accessory. If its CT input or wiring differs from the transformer design, indication and control outputs will not behave as intended.
Transformer WTI Replacement Procedure, Step by Step
Work should follow the transformer manufacturer’s procedures and site electrical safety requirements. The workflow below stays at engineering level and does not replace site permits, isolation procedures or the manufacturer’s instructions.
- Record the existing WTI nameplate and wiring. Capture model, range, supply, contact and output details from the nameplate and drawings.
- Photograph and label terminal connections. Mark every conductor so reconnection follows the original circuit.
- Confirm temperature range and sensing arrangement. Check dial scale, bulb size, thread, capillary length, CT secondary current and heater setting.
- Check alarm, trip and cooling-control logic. Identify what each contact switches and obtain approved set points from the transformer protection documents.
- Verify replacement power supply and outputs. Match supply voltage, contact ratings, analog signal type and communication interface to the panel.
- Confirm panel dimensions and mounting. Compare cutout, hole pattern, rear depth and capillary route with the final drawing of the replacement.
- Install and reconnect the replacement unit. Fill the thermometer pocket with transformer oil, seat the bulb at the bottom and secure the capillary, then reconnect conductors against the labelled photographs. CT secondary circuits must never be opened while the transformer is energized.
- Verify indication, alarms, cooling control and trip logic. Compare the reading with a reference thermometer, test each contact and confirm signals reach the annunciator, PLC or SCADA. Coordinate trip circuit testing with site procedures so no unintended operation occurs.
Direct Replacement or Upgrade?
Many replacements are like-for-like, but changed requirements can justify a different configuration. The decision depends on what the existing system still does well and what it can no longer deliver.
When Direct Replacement Fits
- The existing instrument has failed, but the cooling, alarm and trip architecture still works as designed
- Range, contacts, supply and mounting can be matched one-to-one
- No new remote signals are needed
When an Upgrade Makes More Sense
- Remote signal output is needed, such as Pt100 or 4-20 mA
- RS485 communication is required for monitoring panels or SCADA
- Alarm integration with a control system needs improvement
- The existing model is discontinued or spare parts are hard to source
- Several instruments across a site or fleet are being modernized together
Available functions depend on the specific model. BWR2 instruments, for example, can be paired with a BWX digital display for 4-20 mA output and RS485 communication, but each option has to be confirmed for the chosen configuration. Where direct hot-spot data is the goal, transformer winding temperature monitoring with fiber optic probes is a different class of solution: probes are normally embedded during manufacture or rewind, so an in-service transformer is usually upgraded through its WTI and signal interface instead.
Transformer WTI Replacement Checklist
Use the list below to collect every item before requesting a quotation.
□ Existing model number
□ Temperature range
□ Sensor / input type
□ Power supply
□ Alarm contacts
□ Trip contacts
□ Cooling control contacts
□ Analog output
□ RS485 / communication
□ Panel cutout
□ Mounting depth
□ Terminal diagram
□ Existing sensor compatibility
□ Required spare parts
□ Transformer protection logic
Frequently Asked Questions
Can I replace a transformer WTI with a different model?
Yes, potentially, but temperature range, sensing arrangement, power supply, relay logic, outputs and mechanical dimensions must be compatible. A shared series name such as BWR is not proof of compatibility, so each model needs to be checked against the existing instrument.
What should I check before replacing a winding temperature indicator?
Record the model number, temperature range, sensor and CT input, power supply, alarm, trip and cooling contacts, analog and communication outputs, panel cutout, mounting depth and terminal diagram. Confirm also that the instrument is a WTI and not an OTI.
Can the existing transformer temperature sensor be reused?
Possibly, depending on sensing principle, condition and compatibility with the new WTI. Bulb size, thread, capillary condition and the CT heater arrangement must all match, and damaged capillaries or dry pockets are better replaced.
Do alarm and trip settings need to stay the same after WTI replacement?
Settings should follow transformer protection requirements and approved site or manufacturer logic, not simply be copied without verification. New instruments commonly ship with factory standard set points, so every contact needs its approved value entered and tested.
When should an old WTI be upgraded instead of directly replaced?
Upgrade when communication, output, spare-parts availability or system integration requirements have changed. If the old unit has simply failed and the system around it works, direct replacement is usually simpler.
Need Help Replacing a Transformer Winding Temperature Indicator?
Send the existing WTI model and nameplate photo, transformer type, temperature range, terminal diagram, alarm, trip and cooling-control requirements, power supply, output or communication needs and panel dimensions. With those details FJINNO can match a BWR-series replacement configuration or confirm which parameters need to change.