- Transformer gas relays (Relais Buchholz) provide critical early-warning protection by detecting gas accumulation and oil flow abnormalities in transformateurs immergés dans l'huile
- Complet QJ series range from QJ1-25 to QJ20-80A covers transformers from small distribution units to large power transformers with capacities exceeding 100MVA
- Selection depends on transformer capacity, pipe diameter (25mm, 40mm, 50mm, 80mm), and special requirements like temperature compensation (TH models) or gas sampling capability
- Models with gas sampling boxes (QJ5-80A, QJ13-80A, QJ19-80A, QJ20-80A) enable convenient dissolved gas analysis without oil drainage
- Professional manufacturers with proven track records since 2011 ensure compliance with international standards and provide comprehensive technical support for global projects
Table des matières
- What is a Transformer Gas Relay
- How Transformer Buchholz Relays Work
- Complete QJ Series Model Guide
- Guide de sélection et spécifications techniques
- Guide d'installation et de remplacement
- Normes de qualité et certifications
- Pourquoi choisir Fuzhou Innovation Electronic
- Foire aux questions
- Obtenez un devis aujourd'hui
1. What is a Transformer Gas Relay

UN relais de gaz de transformateur, communément appelé un Relais Buchholz, sert de dispositif de protection installé dans le tuyau de raccordement entre le réservoir principal du transformateur et le réservoir du conservateur. Ce composant essentiel surveille transformateurs immergés dans l'huile pour les défauts internes en détectant l’accumulation de gaz et les conditions anormales de débit d’huile.
1.1 Définition et fonctions principales
Le relais à gaz pour transformateur la protection fonctionne selon un principe simple mais efficace: lorsque des défauts internes surviennent au sein du transformateur, comme une surchauffe, décharge partielle, ou rupture d'isolation, des gaz sont générés et montent à travers le pétrole. Le relais de gaz de transformateur capture ces gaz et déclenche des alarmes ou des disjoncteurs en fonction de la gravité du défaut.
1.2 Application dans les transformateurs immergés dans l'huile
Relais à gaz pour transformateur immergé dans l'huile sont des dispositifs de sécurité obligatoires pour les transformateurs d'une puissance nominale supérieure à 800 kVA dans la plupart des normes internationales. Ils offrent une protection en deux étapes: alarme de gaz légère pour les défauts mineurs, laissant du temps pour l'enquête, et déclenchement de gaz important en cas de défauts graves nécessitant une déconnexion immédiate. Le relais de gaz du transformateur principal dans les sous-stations et les centrales électriques représente la première ligne de défense contre les pannes catastrophiques.
1.3 Distinction par rapport aux autres dispositifs de protection
Alors que relais de protection de transformateur inclure différents types tels que des relais différentiels, relais de surintensité, et relais de température, le transformateur relais Buchholz détecte de manière unique les défauts internes avant qu'ils ne se transforment en anomalies électriques mesurables de l'extérieur. Le relais de pression soudaine du transformateur ne réagit qu'aux changements rapides de pression, whereas gas relays detect both gradual gas accumulation and sudden oil surges.
2. How Transformer Buchholz Relays Work

2.1 Gas Accumulation Detection Mechanism
The upper chamber of the relais de gaz de transformateur contains a float that normally sits in the upper position when filled with oil. As gases generated by internal faults accumulate, they displace the oil, causing the float to drop. This movement closes a mercury switch or microswitch, triggering the light gas alarm circuit. The gas collection chamber allows sampling for dissolved gas analysis, helping identify fault types.
2.2 Oil Flow Velocity Monitoring
The lower chamber houses a hinged flap or vane positioned in the oil flow path. During normal operation, oil flows slowly without deflecting the vane. Cependant, sudden internal faults like winding flashovers or core failures generate rapid gas evolution, créant une poussée de débit d'huile du réservoir principal vers le conservateur. Cette poussée dévie la girouette, activer le contact de déclenchement des gaz lourds qui déconnecte immédiatement le transformateur.
2.3 Double système de protection
Relais de protection contre les gaz du transformateur fournir des niveaux de réponse gradués. Protection contre les gaz légers (typiquement 200-300 accumulation de cm³) signale des problèmes en développement tels que des fuites d'huile lentes, connexions desserrées provoquant un échauffement localisé, ou décharges partielles mineures. La protection contre les gaz lourds réagit aux vitesses d'écoulement du pétrole dépassant 0.6-1.2 MS, indiquant un arc interne grave, pannes d'enroulement, ou défauts centraux nécessitant une isolation immédiate.
3. Complete QJ Series Model Guide

3.1 Série QJ1 – Modèles standards
Le fondamental Relais série QJ1 établir la base de référence pour relais de transformateur protection. Disponible dans plusieurs configurations de diamètres de tuyaux, ces modèles conviennent aux transformateurs de distribution et aux transformateurs de puissance plus petits:
Relais QJ1-25: Conçu pour les tuyaux de 25 mm de diamètre, adapté aux transformateurs jusqu'à 1600kVA. Construction compacte idéale pour les transformateurs de distribution montés sur poteau et sur socle.
QJ1-40: Convient aux tuyaux de 40 mm pour les transformateurs de la gamme 1 600-6 300 kVA. Largement spécifié pour les transformateurs d'installations industrielles et les sous-stations secondaires.
Relais QJ1-50 et QJ1-50A: Modèles standard de 50 mm pour transformateurs de 6,3 MVA à 31,5 MVA. Le “UN” la désignation indique une étanchéité améliorée et une fiabilité de contact améliorée pour les environnements exigeants.
Relais QJ1-80 et QJ1-80A: Variantes robustes de 80 mm pour transformateurs de puissance allant de 31,5 MVA à 120 MVA. Dispose d'une construction robuste résistant à des débits d'huile plus élevés et aux fluctuations de pression courantes dans les grandes unités..
3.2 Série QJ1 avec compensation de température
Les variations de température affectent la densité du pétrole et la solubilité du gaz, pouvant provoquer des alarmes intempestives. Le TH (Temperature compensated, High precision) variants address this challenge:
QJ1-50TH, QJ1-50-TH: Incorporate bimetallic elements that adjust alarm setpoints based on ambient temperature, reducing false positives in regions with significant temperature swings. The hyphenated designation (-ÈME) represents the newer manufacturing standard with improved calibration stability.
QJ1-80TH, QJ1-80-TH: Large transformer applications benefit from temperature compensation as oil volume expansion in 80mm systems can simulate gas accumulation. These models maintain accurate detection across -40°C to +60°C ambient conditions.
3.3 QJ1G Improved Series
Le “G” designation indicates Gaijin (improved) versions incorporating design refinements based on decades of field experience:
QJ1G-50-TH, QJ1G-50TH: Enhanced internal baffle design improves gas-oil separation efficiency. Le mécanisme à flotteur modifié réduit l'hystérésis mécanique pour une activation d'alarme plus cohérente. Les matériaux de contact améliorés prolongent la durée de vie dans les applications à commutation élevée.
QJ1G-80-TH, QJ1G-80A avec boîte d'échantillonnage de gaz, QJ1G-80TH: Les caractéristiques haut de gamme incluent des composants internes en acier inoxydable résistant aux produits de dégradation de l'huile., fenêtres de visualisation usinées avec précision pour une inspection visuelle, et ports d'échantillonnage de gaz intégrés en option. Le QJ1G-80A la variante comprend spécifiquement une boîte d'échantillonnage installée en usine éliminant les besoins de modification sur le terrain.
3.4 Série milieu de gamme QJ2-QJ4
Série QJ2
Relais QJ2-40: Optimisé pour les applications de 40 mm où les contraintes d'espace limitent les options d'installation. Le profil vertical compact convient aux installations d'appareillage intérieures.
Relais QJ2-50, QJ2-80, QJ2-80A: Modèles de capacité moyenne dotés d'une conception à double chambre avec contacts indépendants pour les gaz légers et lourds. Le Relais QJ2-80 domine les installations de transformateurs de 50 à 80 MVA dans les complexes industriels et les sous-stations collectrices de parcs éoliens.
QJ2-80-TH: La version à compensation de température maintient la précision dans les installations extérieures soumises au rayonnement solaire direct et aux températures saisonnières extrêmes.
Série QJ3
QJ3-40, QJ3-80, Relais QJ3-80: Caractérisé par une orientation de montage horizontale, ces modèles conviennent aux applications de rénovation où il existe des limites de dégagement vertical. Le QJ3-80A et QJ3-80-TH les variantes combinent une étanchéité améliorée avec une compensation de température.
QJ3-80A-TH: Configuration Premium intégrant toutes les fonctionnalités avancées—”UN” composants de qualité, compensation de température, et des intervalles d'étalonnage étendus adaptés aux transformateurs d'infrastructures critiques nécessitant 99.9% disponibilité.
Séries QJ4 et QJ4G
Relais QJ4-25, QJ4-25TH: Options de plus petit diamètre pour les applications spécialisées, notamment les transformateurs de traction, transformateurs de four, et sous-stations mobiles compactes.
Relais QJ4-50, QJ4-50-TH, QJ4-50TH: Modèles standard de capacité moyenne avec mécanisme de volet à réponse rapide réduisant le temps de déclenchement de 15-20% par rapport à la série QJ1. Critique pour les applications où la vitesse de résolution des pannes a un impact direct sur l'étendue des dommages à l'équipement.
Relais QJ4-80, QJ4-80-TH, QJ4-80TH: Modèles robustes intégrant des ensembles de volets renforcés résistant à des vitesses d'huile dépassant 2 m/s lors de défauts internes graves.
QJ4G-25, QJ4G-25TH, QJ4G-50TH: Amélioré “G” variantes dotées d'une construction en alliage résistant à la corrosion pour les installations côtières et les environnements industriels avec des contaminants atmosphériques agressifs.
QJ4G-80-TH, QJ4G-80A avec boîte d'échantillonnage de gaz, QJ4G-80TH: Modèles haut de gamme combinant toutes les améliorations. Le boîtier de prélèvement de gaz intégré dans QJ4G-80A permet une analyse de routine des gaz dissous sans interruption de service, soutenir les programmes de maintenance prédictive.
3.5 Série robuste QJ5-QJ20 pour transformateurs de puissance de grande taille
Gamme QJ5-QJ10
QJ5-40, QJ5-50, QJ5-80: Point d'entrée pour la protection des grands transformateurs, évalué pour les unités 80-250MVA. Le boîtier moulé robuste résiste aux contraintes d'installation lors d'un assemblage de transformateur lourd.
QJ5-80A avec boîte d'échantillonnage de gaz: Le système d'échantillonnage intégré en usine comprend des vannes d'isolement, port d'échantillonnage, et cylindre collecteur gradué. Particulièrement précieux pour le GSU (Augmentation du générateur) transformateurs où la tendance des gaz dissous identifie rapidement les problèmes de refroidissement du stator.
QJ6-50, QJ6-80: Modèles à sensibilité améliorée détectant des volumes de gaz aussi faibles que 150 cm³, fournir une alerte plus précoce en cas de défauts se développant lentement dans des transformateurs vieillissants.
QJ7-50, QJ7-80: Spécialisé pour les transformateurs convertisseurs HVDC où les courants harmoniques génèrent des signatures de défauts uniques. Modified gas accumulation curves account for normal gas generation under non-sinusoidal loading.
QJ8-50, QJ8-80: High-pressure rated variants for transformers operating at elevated conservator pressures. Reinforced seals and pressure-balanced design maintain accuracy up to 0.3MPa static head.
QJ9-25, QJ9-50, QJ9-80: Multi-contact configurations providing separate alarm circuits for SCADA integration, local annunciation, and circuit breaker trip logic. Le QJ9-25 serves specialized rectifier transformer applications.
QJ10-50, QJ10-80: Extended-range temperature compensation (-50°C à +70°C) for extreme climate installations from Arctic mining operations to Middle Eastern substations.
QJ11-QJ15 Series
QJ11-50, QJ11-80: Explosion-proof certified variants meeting IECEx and ATEX requirements for installations in hazardous classified areas such as petrochemical plants and offshore platforms.
QJ12-80A avec boîte d'échantillonnage de gaz: Comprend un système de purge automatisé empêchant l'entrée d'air pendant les procédures d'échantillonnage. Maintient l’intégrité de l’échantillon pour une analyse chromatographique précise.
QJ13-25, QJ13-80, QJ13-80TH: Modèles prêts pour le numérique avec contacts auxiliaires prenant en charge les systèmes de surveillance à distance. État des déclenchements et des alarmes transmis aux salles de contrôle centralisées via des liaisons SCADA câblées ou à fibre optique.
QJ13-80A avec boîte d'échantillonnage de gaz: Solution de surveillance de transformateur haut de gamme combinant transformateur de relais de gaz protection avec capacité d'échantillonnage intégrée. Réduit les coûts de maintenance en éliminant les installations de vannes d'échantillonnage séparées.
QJ14-50, QJ14-80: Conceptions nécessitant peu d’entretien avec mécanismes de contact autonettoyants. Intervalles d'entretien prolongés à partir de 5 à 10 années réduisent les coûts du cycle de vie des grands parcs de transformateurs.
QJ15-50: Configuration de montage horizontal spécialisée pour les installations à espace limité telles que les chambres fortes souterraines et les sous-stations urbaines avec un dégagement vertical limité.
Gamme Premium QJ16-QJ20
QJ16-50, QJ16-80: Modèles compatibles avec microprocesseur avec modules de sortie statiques fournissant des contacts sans tension, 4-20Sorties analogiques mA, et options de communication Modbus.
QJ17-50, QJ17-80: Unités qualifiées sismiques conformes à l'IEEE 693 exigences de niveau de performance élevé pour les sous-stations situées dans les régions sujettes aux tremblements de terre. Les composants internes montés sur amortisseurs maintiennent la fonctionnalité grâce à une accélération maximale au sol de 0,5 g..
QJ18-80: Modèle ultra-robuste pour les plus gros transformateurs de puissance (500AMIU+) et autotransformateurs dans les réseaux de transport. Chambre à gaz surdimensionnée (2000 cm³) s'adapte à la production de gaz à partir de volumes de bobinage importants.
QJ19-80, QJ19-80A avec boîte d'échantillonnage de gaz, QJ19-80A-TH: Variantes de haute précision avec précision d'étalonnage ±2 % (par rapport à la norme ±5 %). Critique pour les transformateurs où les exigences d’assurance imposent des systèmes de protection améliorés. Le QJ19-80A-TH représente la configuration phare avec toutes les fonctionnalités premium intégrées.
QJ20-25, QJ20-50, QJ20-80A avec boîte d'échantillonnage de gaz: Dernière génération intégrant les leçons de millions d’heures de service dans le monde. La conception modulaire simplifie le stockage des pièces de rechange : assemblages flottants, mécanismes à palettes, et échange de blocs de contact dans toutes les gammes de tailles, réduisant les coûts d'inventaire.
3.6 Modèles de fonctions spéciales
Échappement automatique QJF1-50-TH: La conception révolutionnaire à ventilation automatique élimine la purge manuelle de l'air pendant la mise en service et après la maintenance. La soupape de ventilation automatique contrôlée par flotteur expulse l'air emprisonné tout en empêchant l'huile de s'échapper.. Réduit le temps de mise en service de 60% et élimine une source courante d'erreurs d'installation provoquant de faux déclenchements.
QJM-40: Variante certifiée marine répondant à DNV-GL, ABS, and Lloyd’s Register requirements for shipboard transformers. Vibration-resistant design withstands constant engine-induced motion and shock loads during heavy weather.
QYW9-I: Oil quality monitoring relay combining gas detection with moisture content sensing. Dual-function protection particularly valuable for hermetically sealed transformers where conservator breathing introduces humidity.
Transformer gas relay guide box: Standardized interface accessory connecting the relay gas sampling port to external DGA (Analyse des gaz dissous) équipement de surveillance. Includes pressure regulators, filters, and quick-disconnect fittings enabling hot-swappable connections during online monitoring system upgrades.
3.7 International Brand Comparison
Qualitrol relay products set industry benchmarks, but QJ series models offer compelling advantages. While Qualitrol 206 et 208 series dominate North American markets with UL/CSA listings, Les modèles QJ offrent des performances techniques équivalentes à 40-50% coûts d'acquisition inférieurs. Le QJ13-80A concurrence directement Qualitrol 208-024, offrant une sensibilité comparable avec les avantages supplémentaires de l'échantillonnage de gaz intégré et de la compensation de température en tant que fonctionnalités standard plutôt que des options coûteuses.
4. Guide de sélection et spécifications techniques

4.1 Matrice de sélection de la capacité du transformateur
Approprié relais de transformateur la sélection commence par l'adaptation du diamètre du tuyau à la valeur nominale du transformateur. Le volume de circulation d'huile et les taux de génération de gaz de défaut varient en fonction de la capacité du transformateur., dicter la taille minimale des tuyaux:
25relais mm (QJ1-25, QJ4-25, QJ9-25, QJ13-25, QJ20-25): Transformateurs de distribution ≤1600kVA. Un volume d'huile limité entraîne une faible génération de gaz, même en cas de panne, nécessitant une détection sensible dans des chambres plus petites.
40relais mm (QJ1-40, QJ2-40, QJ3-40, QJ5-40, QJM-40): Petits transformateurs de puissance 1600-6300kVA. Commun dans les installations industrielles, bâtiments commerciaux, et sous-stations de distribution rurales.
50relais mm (Séries QJ1-50 à QJ20-50): Transformateurs de moyenne puissance 6,3-80MVA. Représente la gamme de tailles la plus largement installée couvrant les transformateurs de sous-stations publics typiques et les transformateurs de grandes installations industrielles.
80relais mm (Séries QJ1-80 à QJ20-80): Gros transformateurs de puissance >80AMIU. Indispensable pour les sous-stations de transport, transformateurs élévateurs de générateur, et réseaux de distribution d'électricité en vrac. Modèles avec “UN” désignation obligatoire au-dessus de 250 MVA en raison des vitesses extrêmes d'écoulement de l'huile lors de pannes.
4.2 Exigences relatives à la boîte d'échantillonnage de gaz
Modèles équipés de boîtes de prélèvement de gaz (QJ5-80A, QJ12-80A, QJ13-80A, QJ19-80A, QJ20-80A, ainsi que diverses variantes QJ1G et QJ4G) convient aux applications où l'analyse des gaz dissous fait partie des protocoles de maintenance de routine. Les services publics exploitant des parcs de transformateurs dépassant 100 les unités réalisent des économies significatives grâce aux tests DGA internes plutôt qu'à l'externalisation des analyses en laboratoire. The integrated sampling box eliminates dedicated sampling valves, reducing leak points and simplifying piping layouts.
4.3 Temperature Compensation Benefits
TH-suffix models prevent nuisance alarms in these scenarios:
Geographic regions with daily temperature swings >20°C cause oil expansion/contraction mimicking gas accumulation. Desert installations, tropical climates with afternoon thunderstorms, and high-altitude locations experience this phenomenon.
Seasonal temperature transitions (spring warming, autumn cooling) generate false alarms as dissolved gases come out of solution with temperature changes. TH models automatically adjust alarm thresholds compensating for these effects.
Outdoor transformers with dark-colored tanks absorb solar radiation, creating localized hot spots. Temperature compensation prevents solar-induced trips during peak sunlight hours.
4.4 Tableau de comparaison des spécifications techniques
| Paramètre | Série QJ1 | Série QJ4/QJ4G | Série QJ13-QJ20 |
|---|---|---|---|
| Volume de gaz léger | 200-300 cm³ | 150-250 cm³ | 150-200 cm³ |
| Vitesse de déclenchement du débit d'huile | 0.9-1.2 MS | 0.7-1.0 MS | 0.6-0.9 MS |
| Contacter l'évaluation | 5Un @ 250VAC | 10Un @ 250VAC | 10Un @ 250VAC |
| Température de fonctionnement | -25°C à +55°C | -40°C à +60°C | -50°C à +70°C |
| Évaluation du boîtier | IP54 | IP65 | IP65/IP67 |
| Intervalle d'étalonnage | 5 années | 7 années | 10 années |
5. Guide d'installation et de remplacement
5.1 Exigences relatives à la position et à l'angle d'installation
Transformer gas relays doit être installé dans la canalisation reliant le réservoir principal au conservateur avec des tolérances angulaires strictes. Le tuyau doit être incliné vers le haut vers le conservateur à 2-4% grade (1.1-2.3 degrés), permettant aux gaz de migrer naturellement vers le relais. Le boîtier du relais doit être monté parfaitement de niveau (Déviation maximale de ± 0,5 degrés) vérifié avec un niveau à bulle de précision lors de l'installation. Même une légère inclinaison provoque des erreurs d'étalonnage : une inclinaison de 2 degrés décale le point de consigne de l'alarme de gaz léger d'environ 50 cm³.
Des longueurs minimales de tuyau droit de 5 × diamètre de tuyau en amont et 3 × diamètre de tuyau en aval garantissent un écoulement d'huile laminaire à travers le relais.. Coudes, vannes, ou des restrictions au sein de ces zones créent des turbulences déclenchant de faux déclenchements de gaz lourds. Pour QJ1-80A installation, cela nécessite une tuyauterie d'entrée droite de 400 mm et une tuyauterie de sortie droite de 240 mm.
5.2 Recommandations sur le cycle de remplacement
Standard relais de protection de transformateur durée de vie 15-20 années dans des conditions normales de fonctionnement. Des calendriers de remplacement accélérés s'appliquent aux environnements difficiles:
Emplacements à courant de défaut élevé (réseaux de transmission, interconnexions des générateurs): 12-15 années en raison des contraintes mécaniques dues aux marées noires répétées.
Ambiances côtières/industrielles: 10-12 années car les contaminants corrosifs dégradent les joints et les contacts malgré les boîtiers IP.
Environnements à températures extrêmes: 12-15 années en cas de fonctionnement proche des limites de température supérieure/inférieure, même avec compensation TH.
Les critères de remplacement basés sur l'état comprennent: fuite d'huile visible autour du voyant ou des entrées de câbles, résistance de contact supérieure à 0,5Ω (mesuré annuellement), échec du test d'étalonnage, ou dommages mécaniques dus à des impacts externes.
5.3 Procédures de test et de mise en service
Les tests de pré-mise sous tension vérifient transformateur relais Buchholz opération. Le test des gaz légers consiste à injecter lentement de l'air à travers le robinet de test supérieur jusqu'à ce que le flotteur descende., déclenchement du contact d'alarme. Enregistrer le volume de gaz réel requis (doit correspondre à la plaque signalétique ±10 %). Les tests de gaz lourds inclinent momentanément l’ensemble du transformateur pour créer une poussée d’huile, ou utilise le levier de test dédié pour dévier manuellement le volet, confirmation de la fermeture du contact de déclenchement.
Après test, évacuer complètement l'air de la chambre du relais à l'aide du robinet de vidange inférieur tout en observant le voyant. Les bulles d'air piégées provoquent de fausses alarmes lors de la mise sous tension initiale. La dernière étape consiste à vérifier la continuité du câblage depuis les contacts du relais jusqu'aux circuits d'alarme/déclenchement du panneau de commande en utilisant une basse tension. (12-24V) signaux de test.
5.4 Erreurs d'installation courantes
Les installateurs montent fréquemment des relais avec une légère inclinaison, Je ne sais pas que cela affecte l'étalonnage. Vérifiez toujours le niveau dans les deux axes à l'aide d'instruments de précision. Une autre erreur courante concerne le support inadéquat des tuyaux : des tuyaux flexibles ou des conduites non soutenues permettent des vibrations et des mouvements qui neutralisent les mécanismes de clapets sensibles.. Installez une tuyauterie en acier rigide avec des supports tous les 1.5-2 mètres.
Un serrage excessif des anneaux de retenue du voyant fissure le verre, entraînant des fuites d'huile.. Suivre les spécifications de couple du fabricant (typiquement 8-12 Nm pour les modèles 80 mm). Le fait de ne pas purger complètement l'air avant la mise sous tension provoque des alarmes intempestives immédiates nécessitant une mise hors tension et une remise en service..
6. Normes de qualité et certifications
6.1 Conformité aux normes internationales
Transformer gas relays fabriqué selon CEI 60076-18 les spécifications garantissent une interopérabilité mondiale et des caractéristiques de performance constantes. Cette norme définit les méthodes d'essai pour la vérification de la sensibilité, contacter la fiabilité, capacité de tenue sismique, et endurance environnementale. Une conformité supplémentaire aux exigences IEEE C57.12.00 garantit l'adéquation aux applications de services publics nord-américaines lorsque cela est spécifié.
Les protocoles de tests de type valident les performances dans des températures extrêmes, profils de vibration simulant des événements de transport et sismiques, et tests de résistance diélectrique confirmant un fonctionnement sûr à proximité des composants du transformateur haute tension. Les tests en usine comprennent 100% vérification fonctionnelle : chaque relais est soumis à des tests de défaut simulés avant l'expédition.
6.2 Processus de contrôle qualité
Moderne fabricants de relais de transformateur utiliser un contrôle statistique des processus en surveillant les dimensions critiques et les couples d'assemblage. Des stations de test automatisées font passer chaque relais 50 simulations de gaz légers et de gaz lourds, cohérence de l'actionnement de l'enregistrement. Les tests de résistance de contact à des courants de 10 mA et 1 A identifient les mécanismes de commutation défectueux. Les tests de pression jusqu'à 2 fois la pression nominale confirment l'intégrité du joint empêchant les fuites d'huile pendant des décennies de service..
6.3 Comparaison avec les marques internationales
Alors que Relais Qualitrol jouir d’une forte reconnaissance de marque, notamment en Amérique du Nord, Les modèles de la série QJ correspondent ou dépassent les spécifications techniques. Des tests indépendants confirment que la sensibilité QJ est égale à Qualitrol dans les limites de l'incertitude de mesure. Les tests de durée de vie des contacts démontrent la survie des modèles QJ >10,000 opérations mécaniques contre 8 000 opérations pour des unités importées comparables.
Le principal différenciateur réside dans les coûts du cycle de vie. Coût des pièces de rechange de la série QJ 30-40% inférieur aux équivalents Qualitrol. Support technique local en Asie, Afrique, et l'Amérique latine fournit une réponse plus rapide que de compter sur l'assistance des usines nord-américaines ou européennes. Pour les services publics et les opérateurs industriels gérant de grands parcs de transformateurs, ces facteurs se traduisent par un coût total de possession considérablement inférieur.
7. Pourquoi choisir Fuzhou Innovation Electronic Scie&Tech Co., Ltée.
7.1 Une expertise établie depuis 2011
Avec des opérations commençant dans 2011, notre entreprise apporte 13 années d'expérience spécialisée dans relais de protection de transformateur fabrication. Cette longue expérience se traduit par une fiabilité éprouvée : nos relais protègent des milliers de transformateurs à travers le monde. 60+ pays sur chaque continent habité. Premières installations de 2011-2013 continuer à fonctionner de manière fiable, valider nos allégations de longévité de conception.
7.2 Gamme de produits complète
En tant que dévoué usine de relais de transformateur, nous maintenons un inventaire complet de la série QJ à partir de QJ1-25 à travers QJ20-80A. Cela élimine les complications liées à plusieurs fournisseurs : achetez tous les relais de protection pour une sous-station entière auprès d'une seule source.. Documentation standardisée, niveaux de qualité constants, et un support technique unifié simplifient la gestion des achats et du cycle de vie.
Notre gamme de produits s'étend au-delà des relais à gaz pour inclure des dispositifs de décompression, indicateurs de niveau d'huile, moniteurs de température, et ensembles complets d'accessoires pour transformateurs. Les achats groupés donnent droit à des remises sur volume tout en garantissant la compatibilité des composants vérifiée par des tests d'intégration en usine.
7.3 Services d'assistance technique et de personnalisation
L’assistance technique commence lors de l’élaboration des spécifications. Nos ingénieurs d'application examinent les paramètres du transformateur, conditions de fonctionnement, et philosophie de protection pour recommander des configurations de relais optimales. Étalonnages personnalisés, supports de montage spéciaux, et les évaluations environnementales modifiées répondent à des exigences uniques au-delà des spécifications du catalogue..
Le support après-vente comprend la supervision de l'installation, aide à la mise en service, et programmes de formation pour le personnel de maintenance. Assistance dépannage par téléphone, e-mail, ou la vidéoconférence résout les problèmes rapidement. La couverture de la garantie s'étend 24 mois à compter de la date de mise en service (36 mois à compter de l'expédition), dépassant les périodes de 12 mois standard de l’industrie.
7.4 Logistique globale et service après-vente
Des partenariats d'expédition stratégiques avec les principaux transporteurs garantissent une livraison fiable vers des destinations mondiales. Plages de délais de livraison standards 3-4 semaines pour les articles du catalogue, avec expédition accélérée sous 10 jours disponible pour les besoins urgents. L'emballage d'exportation répond aux normes NIMP-15 pour le bois sans fumigation, et des caisses résistantes aux intempéries classées IP65 protègent les relais pendant le transport maritime et le stockage extérieur sur les sites du projet..
Nous disposons de centres de service dans les régions clés fournissant un stock local de pièces de rechange et une assistance sur le terrain.. Garanties prolongées et contrats de maintenance préventive disponibles pour les installations critiques nécessitant une disponibilité maximale. Les services d'étalonnage annuels peuvent être regroupés avec l'achat d'équipement, simplifier la planification budgétaire à long terme.
8. Foire aux questions
Quelle est la différence entre les relais des séries QJ1 et QJ1G?
QJ1G représente une génération améliorée intégrant des améliorations de conception basées sur l'expérience sur le terrain. Key enhancements include optimized internal baffle geometry improving gas-oil separation efficiency by approximately 15%, upgraded float mechanisms reducing mechanical hysteresis, and improved contact materials extending electrical life. While QJ1 series provides reliable service for standard applications, QJ1G models suit demanding installations where maximum sensitivity and longevity justify slightly higher initial costs.
What advantages do models with gas sampling boxes offer?
Integrated gas sampling boxes like those on QJ5-80A, QJ13-80A, et QJ19-80A models enable dissolved gas analysis without draining transformer oil or installing separate sampling valves. This capability supports predictive maintenance programs identifying developing faults before catastrophic failure. Un échantillonnage mensuel ou trimestriel de routine établit des données de tendance guidant les décisions de gestion de la charge et la planification de la maintenance.. La conception intégrée élimine les points de fuite potentiels par rapport aux systèmes d'échantillonnage installés sur le terrain, améliorant la fiabilité globale tout en réduisant les coûts de main-d'œuvre d'installation en 4-6 heures par transformateur.
Quand faut-il remplacer un relais de gaz de transformateur?
Remplacer les relais présentant des dommages physiques (voyant fissuré, logement bosselé, bornes corrodées), fuite d'huile quelle que soit la quantité, échec du test d'étalonnage montrant >15% écart par rapport aux paramètres de la plaque signalétique, ou résistance de contact supérieure à 0,5Ω. Même en l'absence de défauts visibles, envisager le remplacement après 15-20 ans pour les modèles standards ou 12-15 années dans des environnements difficiles (côtier, industriel, température extrême). Les transformateurs en cours de rénovation majeure reçoivent généralement de nouveaux relais comme assurance contre la défaillance de la vieille protection pendant la durée de vie prolongée prévue pour les unités reconstruites..
Quels sont les délais de livraison et les quantités minimales de commande?
Les articles du catalogue standard sont expédiés dans 20-25 jours ouvrables après la confirmation de la commande. La production accélérée réduit les délais de livraison 10-12 jours pour les besoins urgents avec frais de pointe associés. La quantité minimale de commande est d'une pièce ; nous acceptons également les commandes de remplacement d'unités uniques et les petits projets.. Cependant, commandes dépassant 10 les unités sont admissibles aux niveaux de tarification en volume, avec des réductions allant jusqu'à 20+ unités. Grands projets (50+ relais) recevoir des devis personnalisés reflétant les prix et les calendriers de livraison spécifiques au projet, coordonnés avec les délais de fabrication des transformateurs.
Les relais de la série QJ sont-ils conformes aux normes internationales?
Oui, Les modèles de la série QJ sont conformes à la CEI 60076-18 exigences régissant la conception des relais à gaz des transformateurs, essai, et performances. Des rapports d'essais de type documentant la conformité sont disponibles sur demande. Certains modèles sont dotés de certifications supplémentaires, notamment IEEE C57.12.00 (Marché nord-américain), IECEx (installations en atmosphère explosive), qualification sismique selon IEEE 693 (régions sujettes aux tremblements de terre), et certifications marines des sociétés de classification (DNV-GL, ABS, Registre du Lloyd's). Spécifiez les certifications requises lors du devis pour garantir une sélection appropriée du modèle.
Puis-je moderniser un relais QJ sur un transformateur utilisant actuellement une marque différente?
Absolument. Les relais QJ présentent des dimensions de montage standardisées et des connexions de tuyaux compatibles avec la plupart des installations existantes. La principale considération consiste à vérifier le diamètre du tuyau (25/40/50/80mm) et sélection du modèle QJ correspondant. Les connexions électriques nécessitent une attention particulière aux valeurs nominales des contacts et à la polarité du câblage., mais les borniers standard s'adaptent à différents calibres de fils et niveaux de tension de commande. Nous fournissons des instructions de mise à niveau détaillées et pouvons examiner les photos du site pour confirmer la compatibilité avant l'achat., éliminer l'incertitude.
9. Obtenez un devis aujourd'hui
Prêt à préciser le droit relais de gaz de transformateur pour votre projet? Notre équipe d’ingénierie d’applications est prête à vous aider dans les sélections techniques, prix compétitif, et un calendrier de livraison aligné sur le calendrier de votre projet.
Fabricant: Science électronique d'innovation de Fuzhou&Tech Co., Ltée.
Établi: 2011
E-mail: web@fjinno.net
WhatsApp/WeChat/téléphone: +86 13599070393
QQ: 3408968340
Adresse: Parc industriel de réseautage de grains U de Liandong, No.12, route Xingye Ouest, Fuzhou, Fujian, Chine
Site web: www.fjinno.net
Contactez-nous avec les spécifications de votre transformateur, y compris la capacité nominale (kVA/TVA), classe de tension, diamètre du tuyau du conservateur, et toute exigence particulière en matière d'environnement ou de certification. Nous vous répondrons dans 24 heures avec recommandations préliminaires et devis détaillés. Fiches techniques, dessins d'installation, et les certificats de test sont fournis avec toutes les citations permettant une prise de décision éclairée.
Pour les projets en cours nécessitant plusieurs installations de transformateurs, nous proposons des contrats d'achat généraux avec des prix verrouillés pour des périodes de 12 mois, protéger votre budget des fluctuations du marché tout en garantissant une allocation prioritaire de la production et une livraison accélérée en cas de besoin.
Clause de non-responsabilité
Les spécifications techniques, paramètres de performances, et les conseils d'application fournis dans ce guide représentent des informations générales basées sur les configurations de produits standard à la date de publication.. Les spécifications réelles du produit peuvent varier en fonction des révisions de fabrication, exigences de personnalisation, et les besoins régionaux en matière de certification.
La conception du système de protection du transformateur doit toujours impliquer des ingénieurs électriciens qualifiés et familiarisés avec les normes applicables. (CEI, IEEE, codes nationaux) et conditions spécifiques au site. The information presented here serves as preliminary guidance for product selection but does not substitute for professional engineering analysis considering fault levels, coordination de la protection, Intégration SCADA, and safety compliance.
Pricing, delivery schedules, and product availability are subject to change based on market conditions, material costs, and production capacity. All quotations remain valid for 30 days unless otherwise specified. Confirm current specifications and pricing with our sales team before finalizing purchase orders.
Installation, essai, and maintenance procedures outlined in this guide provide general orientation but do not replace manufacturer-specific installation manuals, safety protocols, and utility-specific work practices. Always refer to detailed product documentation provided with each relay and follow applicable electrical safety standards during all work activities.
While we maintain rigorous quality control processes, performance in specific applications depends on proper selection, correct installation, and appropriate maintenance. We recommend consulting with our technical support team during project planning to ensure optimal relay configuration for your particular transformer protection requirements.
Capteur de température à fibre optique, Système de surveillance intelligent, Fabricant de fibre optique distribué en Chine
![]() |
![]() |
![]() |